DIN16A DIGITAL INPUT MODULE USER MANUAL SMARTGEN (ZHENGZHOU) TECHNOLOGY CO.,LTD.
Chinese trademark English trademark SmartGen ―make your generator smart SmartGen Technology Co., Ltd No.28 Jinsuo Road, Zhengzhou, Henan Province, China Tel: +86-371-67988888/67981888/67992951 +86-371-67981000(overseas) Fax: +86-371-67992952 Email: sales@smartgen.cn Web: www.smartgen.com.cn www.smartgen.cn All rights reserved.
DIN16A DIGITAL INPUT MODULE USER MANUAL CONTENTS 1 OVERVIEW.................................................................................................................................... 4 2 TECHNICAL PARAMETER ........................................................................................................... 4 3 PROTECTION ............................................................................................................................... 5 3.1 WARNING ........................
DIN16A DIGITAL INPUT MODULE USER MANUAL 1 OVERVIEW DIN16A digital input module is an expansion module which has 16 auxiliary digital input channels and the name of each channel can be defined by users. The input port status collected by DIN16A is transmitted to the HMC9000S controller for processing via CANBUS port. 2 TECHNICAL PARAMETER Table 2 Technical Parameter Item Content Working Voltage DC18.0V~ DC35.0V continuous power supply Power Consumption <2W Case Dimension 107.6mm x 89.7mm x 60.
DIN16A DIGITAL INPUT MODULE USER MANUAL 3 PROTECTION 3.1 WARNING Warnings are not shutdown alarms and do not affect the operation of the gen-set. When DIN16A module is enabled and detects the warning signal, the controller HMC9000S will initiate a warning alarm and the corresponding alarm information will be displayed on LCD. Warning types are as follows: Table 3 Warning Alarm List No.
DIN16A DIGITAL INPUT MODULE USER MANUAL more than 3 seconds will enter the configuration menu, which allows users to set all DIN16A parameters, as follows: Note: Pressing can exit setting directly during setting. Table 5 Parameter Configuration List Items Range Default Values Remarks 1. Input 1 Set (0-50) 0:Not used DIN16A setting 2. Input 1 Type (0-1) 0:Close to activate DIN16A setting 3. Input 2 Set (0-50) 0:Not used DIN16A setting 4.
DIN16A DIGITAL INPUT MODULE USER MANUAL 5 DEFINITION OF INPUT PORT 5.1 DEFINITION CONTENTS OF DIGITAL INPUT Table 6 Definition Contents List of Digital Input NO. Items Contents 1 Function set (0-50) 2 Active Type (0-1) 3 Effective Range (0-3) 4 Effective Action (0-2) 5 Input Delay 6 Display string (0-20.0)s User-defined input port Description More details please refer to Function Setting.
DIN16A DIGITAL INPUT MODULE USER MANUAL No. 2. 3. 4. 5. Function DC input B+ SCR (CANBUS) CAN(H) (CANBUS) CAN(L) (CANBUS) Cable Size Description 2.5mm2 DC power supply positive input. 0.5mm2 Connect CANBUS expansion 0.5mm 2 0.5mm 2 port of port to HMC9000S. Impedance-120Ω shielding wire with its one end grounded is recommended. There is 120Ω terminal resistance inside already; if needed, make terminal 5, 6 short circuits. 6. 120Ω 0.5mm2 7. DIN1 1.0mm2 Digital input 8. DIN2 1.
DIN16A DIGITAL INPUT MODULE USER MANUAL 7 DIN16A TYPICAL APPLICATION Fig.2 Typical Wiring Diagram 8 INSTALLATION Case dimension: Fig.3 Case Dimension and Panel Cutout DIN16A Digital Input Module Version 1.
DIN16A DIGITAL INPUT MODULE USER MANUAL 9 FAULT FINDING Symptom Possible remedy Controller no response with power. CANBUS communication failure Auxiliary input alarm Check starting batteries; Check controller connection wirings; Check wiring. Check wiring. Check if input polarities configuration is correct. _________________________________ DIN16A Digital Input Module Version 1.