5 PROGRAMMABLE PARAMETERS
5.1 CONTENTS AND SCOPES OF PARAMETERS
Table 5 Parameter Content & Scope
No.
Items
Parameters
Defaults
Description
Gateway
1
Site Name
(0-65535)
20 Chinese characters, letters or
numbers
2
URL
(0-65535)
www.monitoryun.com
40 characters
3
Server Port
(0-65535)
91
4
Security Code
(0-65535)
123456
16 characters
GPS
1
GPS Enabled
(0-1)
1
0: Manual Input 1: GPS Location
2
Longitude
((-180)-180)°
0.000000
GPS location, altitude information
3
Latitude
((-90)-90)°
0.000000
4
Altitude
((-9999.9)-9999.9)m
100.0
GSM
1
GSM Enabled
(0-1)
1
0: Disabled; 1: Enabled
2
GPRS Password
Reserved
3
Message Center
Reserved
4
PIN Enabled
(0-1)
0
0: Disabled; 1: Enabled
5
APN
(0-65535)
40 characters
Digital Input
Digital Input 1
1
Setting
(0-9)
0
Default: Not used
2
Type
(0-1)
0
0: Active when close
1: Active when open
See: Table 6 Digital Input Ports
Content
3
Delay
(0-20.0)
0.0
Action delay
Digital Input 2
1
Setting
(0-9)
1
Default: Lamp test
2
Type
(0-1)
0
0: Active when close
1: Active when open
See: Table 6 Digital Input Ports
Content
3
Delay
(0-20.0)
0.0
Action delay
Digital Output
1
Setting
(0-14)
0
Default: Not used
See: Table 7 Relay Output Ports
Content
NOTE: Configuration of monitoring genset controller model, communication port, communication baud rate, and
communication ID need to be set on the platform, and cloud monitoring module needs to restart up after setting.