2. Injection Mode – The normally closed contactor S1 is open. SmartBypass allows the Smart Wires series
compensation devices to inject their reactance across its terminals in series with the line.
7 Product Components
The individual components of the SmartBypass are shown in Figure 7-1.
Figure 7-1: Individual Components of the SmartBypass
A – Protection Circuitry – the Silicon Controlled Rectifiers (SCRs) are housed longitudinally along the interior floor
of the unit.
B – Yoke Plate – this plate is the fixture point for insulators supporting the unit from above.
C – NEMA Pads – these are the electrical connection points for the unit.
D – Corona Rings – surround both latitudinal sides of the device to prevent corona at high voltages.
E – Normally Closed Contactor – the normally closed contactor is housed across the top of the inside of the
enclosure parallel to the yoke plate.
8 Wireless Communication
The SmartBypass has the capability to communicate over a secure wireless Industrial, Scientific and Medical (ISM)
band. The ISM Secure Wireless Mesh is the communication network protocol based on Radio Frequency wireless
communication for between ground-based equipment and the SmartBypass. The SmartBypass support the 900
MHz band in the US. The SmartBypass uses a frequency-hopping spread-spectrum solution. It does not occupy a
single user-selectable-channel like, for example, WiFi does.