Door Input Status
0: Open
1: Closed
40067
Read Only
PIR Status
0: No Movement detected
1: Movement detected
40068
Read Only
Read Write
(3.09+)
0-10V Fan Value
Value / 10 (e.g. 2.1V = 21)
(To write add 10 e.g. - to write2.1v send 1021
40069
Read Only
0-10V Fan Max
Value
0-10v (@*10)
40070
Read /
Write
Digital Input logic
0: Normally Open
1: Normally Closed
40071
Read /
Write
Default Start Temp
Ver 3.3 firmware +
0: Off
15-35c or 59-86F
40072
Read /
Write
Beeper
0: Beeper OFF
1: Beeper On (Default)
40073
Read /
Write
Fan Relay Lock
(Version 40.1+)
0: Off (default)
1: On
This function locks the Fan relay logic to 0-10V
outputs – if enabled depending on other
settings it may cause fan to start and run
before heat or cool calls from the W & Y
relays.
40074
Read /
Write
Temperature
calibration offset
(Version 40.4+)
-9.9 to +10c
This register permits the room temperature to
be offset to correct for perceived room
temperature sensor inaccuracies.
40075
Read /
Write
Temperature
sensor speed of
response.
(Version 40.4+)
0: Very Fast
1: Fast
2: Normal
3: Slow (Default)
4: Very Slow