User Manual

Page 24
40046
Read /
Write
Permitted Modes
0: Off / Auto
1: Off / Heat / Cool / Auto
2: Off / Heat / Cool
3: Off / Heat
4: Off / Cool
5: Off / Auto (display current mode in LCD)
40047
Read /
Write
Swap C/F display
shown on display
0: C/F Button hidden
1: C/F button shown
40048
Read /
Write
Fan Span
0.5C-10 C 0.5C step 1.0F-20 F 1F steps
Data format: Fan span * 10
40049
Read /
Write
0-10 Fan Interval
10-300 seconds in 10 second steps (60
seconds default.
40050
Read /
Write
0-10 Fan Direction
0: 10V is 100% open (forward acting)
1: 0V is 100% open (reverse acting)
40051
Read /
Write
0-10 Fan Minimum
Voltage.
0-10v (Fan value x 10)
40052
Read /
Write
0-10 Heat Interval
10-300 seconds in 10 second steps (60
seconds default.
40053
Read /
Write
0-10 Heat Direction
0: 10V is 100% open (forward acting)
1: 0V is 100% open (reverse acting)
40054
Read /
Write
0-10 Heat
Minimum Voltage
0-10v (Heat value x 10)
40055
Read /
Write
0-10 Cool Interval
10-300 seconds in 10 second steps (60
seconds default.
40056
Read /
Write
0-10 Cool Direction
0: 10V is 100% open (forward acting)
1: 0V is 100% open (reverse acting)
40057
Read /
Write
0-10 Cool Minimum
Voltage
0-10v (Cool value x 10)
40058
Read /
Write
Window input logic
0: Normally Open
1: Normally closed
2: Off (input disabled)
3: Shows FLT (FAULT) shown on LCD
alternating with temperature display.
40059
Read /
Write
Window input
Delay
0-300 seconds in 30 second steps
40060
Read /
Write
Door input logic
0: Off
1: Normally Open
2: Normally closed
40061
Read /
Write
Door input Delay
0-300 seconds in 30 second steps
40062
Read /
Write
PIR input Delay
(Seek Time)
0: Off
1-60 minutes in 1-minute steps
40063
40064
Read /
Write
Unit run time log
0-9999.9 hours
Register 40063 & 40064 are to be used together to determine the total Heat & Cool run time in
0.1 hours.
For example, for a total run time of 15643.4 hours register
40064 will show 434 and register
40063 will show 156
40065
Read Only
Window Input
Status
0: Open
1: Closed