User Manual

Page 20
40011
Read /Write
(Read only
ver +4.04)
Room Temperature
Value / 10 (e.g. 21.7c = 217)
(Writing to the room temp register to
calibrate this value.)
40012
Read /
Write
Temperature
Display
0 = Show Room and Set Temperature
1 = Show Set Temperature Only
40013
Read /
Write
Native C/F Display
0 = Deg C format
1 = Deg F format
40014
Read /
Write
User Set Point High
Limit
5°C to 30°C Range (41°F-86°F) in 1°C/F Steps
1:1
40015
Read /
Write
User Set Point Low
Limit
5°C to 30°C Range (41°f-86°F) in 1°C/F Steps
1:1
40016
Read /
Write
Dead Band
0.5°C to 5.0°C in 0.5°C Steps
1.0°F to 10.0°F in 1°F Steps
Value / 10 (e.g. 1.5°C Dead Band = 15)
40017
Read /
Write
Relay Span
0.5°C to 3.0°C in 0.5°C Steps
1°F to 10°F in 1°F Steps
Value / 10 (e.g. 1.0°C Span = 10)
Version 3 code has this function Inactive.
Modbus will return valid data however this
function is internally disabled. Register
provided for backwards compatibility only.
40018
Read /
Write
Fan Purge Period
0 = Off
1 = Fan Purge - 1 Min
2 = Fan Purge - 3 Min
3 = Fan Purge - 5 Min
4 = Fan Purge - 10 Min
5 = Heat Only Fan Purge - 1 Min
6 = Heat Only Fan Purge - 3 Min
7 = Heat Only Fan Purge - 5 Min
8 = Heat Only Fan Purge - 10 Min
9 = Cool Only Fan Purge - 1 Min
10 = Cool Only Fan Purge - 3 Min
11 = Cool Only Fan Purge - 5 Min
12 = Cool Only Fan Purge - 10 Min
40019
Read /
Write
0-10V Heat Span
0.5°C to 10°C in 0.5°C Steps
1°F to 20°F in 1°F Steps
Value / 10 (e.g. Heat Span of 1°C= 10)
40020
Read /
Write
0-10V Cool Span
0.5°C to 10°C in 0.5°C Steps
1°F to 20°F in 1°F Steps
Value / 10 (e.g. Cool Span of 1°C = 10)
40021
Read /
Write
Auto Off Timer
0 = 0ff
1 to 10 Hours. (0.5 hour steps)
Value / 10 (e.g. 3 Hour Auto Off Timer = 30)
40022
Read /Write
Unoccupied Heat
Set Point
0 = Off
5°C to 30°C in 1.0°C Steps
41°F to 86°F in 1°F Steps
40023
Read / write
Unoccupied Cool
Set Point
0 = Off
5°C to 30°C in 1.0°C Steps
41°F to 86°F in 1°F Steps