User Manual
Page 17
25
Un –Occupied fan mode
Fan 3 Speed mode
1: Low (Auto) (default)
2: Med (Auto)
3: High (Auto)
4: Low (ON)
5: Med (ON)
6: High (ON)
26
Backlight
0: On with button press Only (Default > ver 3.1)
1: Always On high
2: Low when standby / high when active (Default < ver 3.1)
27
TT sensor (SI & Com)
0: Remote – Use this sensor in place of the fitted sensor.
1: Average – Use both remote and fitted sensor and control
to the average temperature of both sensors.
2: Data – Sensor value used for Modbus only.
3: Duct – Used for 2 pipe mode.
28
Temperature Calibration
+/- 10 deg (C or F)
Adjust to show correct room temp.
29
Digital Input
0: Force Room to Unoccupied Mode
1: Chime Door Bell
2: Klixon Mode Enable
30
Digital Input Logic
0: Normally Open
1: Normally Closed
31
Window Input Logic
0: Normally Open
1: Normally closed
2: OFF (Input function disabled)
3: Ver 3.3+ Show FLt (Fault) on LCD (Toggles between
temperature display and “FLt”)
32
Window Input Delay
0 - 300 seconds 30 seconds steps (30 seconds default)
33
Door Input Logic
0: Off (default)
1: Normally open
2: Normally close
34
Door Input Delay
0 - 300 seconds 30 seconds steps (180 seconds default)
35
PIR Input Delay
0: Off (default)
1 – 15 minutes 1 minute steps (ver 3.3 changed 0-60min)
36
Reset Fan
0: Off
1: On
(resets indoor fan to auto every time mode is set to off)
37
Belimo Mode
0: Off 1: On
38
Modbus Address
1-255
39
Baud rate
1: 4800bps
2: 9600bps (default)
3:19200bps
40
Default Start Temp
Version Ver 3.3+
0=OFF (default) 15~35C or 59~86F
41
Beeper
Version Ver 3.9+
0: Off
1: On (default)
42
Fan Relay Lock
(Version 40.1+)
0:Off (default)
1: On
(This function locks the Fan relay logic to 0-10V outputs – if
enabled depending on other settings it may cause fan to start