User Manual
Page 16
5
High temp set limit
5C-30C or 41F-86F (Ver41.0+ 5-50c or 41-122F)
6
Low temp set limit
5C-30C or 41F-86F
7
Dead band
0C-5.0C or 0F-10.0F in 0.1C/0.1F steps.
Depending on Option 3 above.
Data format: Dead band * 10
8
Fan Purge / Run On Period
0: OFF
1: Fan purge - 1 min
2: Fan purge - 3 min
3: Fan purge - 5 min
4: Fan purge - 10 min
5: Heat only fan purge - 1 min
6: Heat only fan purge - 3 min
7: Heat only fan purge - 5 min
8: Heat only fan purge - 10 min
9: Cool only fan purge - 1 min
10: Cool only fan purge - 3 min
11: Cool only fan purge - 5 min
12: Cool only fan purge - 10 min
9
Fan span
0.5C-3.0C/1.0F-6.0F 0.1C/0.1F steps
Data format: Fan span * 10
10
0-10V Fan Interval (PI)
10-300 seconds 10 seconds' steps (60 seconds default)
11
0-10V Fan direction
0: 0 - 10V – slow to fast (Forward Acting)
1: 10 to 0V – slow to fast (Reverse Acting)
12
0-10V Fan minimum value
(Starting fan voltage when
running)
0 -10V
Data format: 0-10V Fan minimum value * 10
13
0-10V Fan Maximum value
(Maximum fan voltage
when running)
0 -10V
Data format: 0-10V Fan minimum value * 10
14
Heat span
0.5C-3.0C/1.0F-6.0F 0.1C/0.1F steps
Data format: Fan span * 10
15
0-10V Heat interval (PI)
10-300 seconds 10 seconds' steps (60 seconds default)
16
0-10V Heat direction
0: 10V is 100% open (forward acting)
1: 0V is 100% open (reverse acting)
17
0-10V Heat minimum
Voltage
0 -10V
Data format: 0-10V Heat minimum value * 10
18
Cool span
0.5C-3.0C/1.0F-6.0F 0.1C/0.1F steps
Data format: Fan span * 10
19
0-10V Cool interval (PI)
10-300 seconds 10 seconds' steps (60 seconds default)
20
0-10V Cool direction
0: 10V is 100% open (forward acting)
1: 0V is 100% open (reverse acting)
21
0-10V Cool minimum
Voltage
0 -10V
Data format: 0-10V Cool minimum value * 10
22
Auto Off Timer
0: No auto off timer
1-10hours 0.5 hour increments.
Data format: hour * 10
23
Un-occupied heat
Set point
0: OFF
5C-30C/41F-86F 0.5C/1F steps
24
Un-occupied cool
Set point
0: OFF
5C-30C/41F-86F 0.5C/1F steps