Installation Instructions
INSTALLATION INSTRUCTIONS FOR EMERGENCY EXIT SIGN
Page 2 of 2
OPERATION (Battery Backup):
1. Apply AC power to the unit. The LED Indicator should turn RED.
2. After the battery has been left to charge for 2 hours, test the unit by pushing the
switch. The LED indicator turns OFF and the LED board stays ON.
3. When the switch is released, the LEDs turn OFF and the LED indicator turns
back to RED.
MAINTENANCE:
Caution: Always turn off AC power to the equipment before servicing. Servicing should be
performed only by a qualified service technician. Use only MANUFACTURER supplied replacement parts.
BATTERY: The battery supplied with the Battery Backup model requires no maintenance. However, it should be tested
periodically (see TESTING) and replaced when it no longer operates the connected fixtures for the duration of a 30-second or
90-minute test. The battery supplied in this equipment has a life expectancy of 5-7 years when used in a normal ambient
temperature of 72ºF.
TESTING:
National Electric Code (NEC) and NFPA life safety code regulations require that routine tests need to be performed as listed below:
Once every month, the unit needs to be tested for duration of 30 seconds. Push in and hold the test switch to perform this test.
Once every 12 months, a full 90 minute (per UL requirements) test needs to be performed on the unit. Disconnect power to the
unit and leave it in the emergency mode. The LEDs should stay ON for atleast 90 minutes.