10 Technical Data
SMA Solar Technology AG
Installation Manual SBxx-1SP-US-41-IA-xx-10 69
SB6.0-1SP-US-41 SB7.0-1SP-US-41 SB7.7-1SP-US-41
Range of the displace-
ment power factor (ad-
justable)
0.8
overexcited
to
0.8
underexcited
0.8
overexcited
to
0.8
underexcited
0.8
overexcited
to
0.8
underexcited
Feed-in phases 1 1 1
Phase connection 2 2 2
Overvoltage category
in accordance with
UL1741
IV IV IV
Efficiency
SB6.0-1SP-US-41 SB7.0-1SP-US-41 SB7.7-1SP-US-41
Maximum efficiency at
208V, η
max
97.2% 97.1% 97.1%
CEC efficiency at 208
V, η
CEC
96.5% 96.5% 96.5%
Maximum efficiency at
240V, η
max
97.6% 97.5% 97.5%
CEC efficiency at 240
V, η
CEC
97.0% 97.0% 97.0%
10.2 AC Output, Secure Power Supply Operation
Maximum AC power 2000W
Nominal AC voltage 120V
AC voltage range 109V to 132V
Maximum output current 16A
Minimum load 1W
10.3 Multifunction Relay
Maximum DC switching voltage 30V
Maximum AC switching current 1.0A
Maximum DC switching current 1.0A
Minimum load 0.1W
Minimum electrical endurance when the maxi-
mum switching voltage and maximum switching
current are complied with*
100000 switching cycles
* Corresponds to 20years at 12switching operations per day