10 Technical Data
SMA Solar Technology AG
Installation Manual SBxx-1SP-US-41-IA-xx-10 65
10 Technical Data
10.1 DC/AC
10.1.1 Sunny Boy 3.0-US / 3.8-US / 5.0-US
DC input
SB3.0-1SP-US-41 SB3.8-1SP-US-41 SB5.0-1SP-US-41
Maximum PV array
power
4800Wp 6080Wp 8000Wp
Maximum input voltage 600V 600V 600V
MPP voltage range 100V to 550V 100V to 550V 100V to 550V
Rated input voltage 155V to 480V 195V to 480V 220V to 480V
Minimum input voltage 100V 100V 100V
Initial input voltage 125V 125V 125V
Maximum input current
per input
10A 10A 10A
Maximum short-circuit
current per input
18A 18A 18A
Maximum input source
reverse current to input
source
0A 0A 0A
Number of indepen-
dent MPP inputs
2 2 3
AC output
SB3.0-1SP-US-41 SB3.8-1SP-US-41 SB5.0-1SP-US-41
Rated power at 208V 3000 W 3328 W 5000 W
Rated power at 240V 3000 W 3800 W 5000 W
Maximum apparent
AC power at 208V
3000VA 3328VA 5000VA
Maximum apparent
AC power at 240V
3000VA 3800VA 5000VA
Rated grid voltage 208 V / 240 V 208 V / 240 V 208 V / 240 V
AC voltage range at
208V
183V to 229V 183V to 229V 183V to 229V
ENGLISH