10 Technical Data
SMA Solar Technology AG
Installation ManualSBxx-1SP-US-41-IA-xx-1068
SB6.0-1SP-US-41 SB7.0-1SP-US-41 SB7.7-1SP-US-41
Maximum apparent
AC power at 208V
5200VA 6650VA 6650VA
Maximum apparent
AC power at 240V
6000VA 7000VA 7680VA
Rated grid voltage 208 V / 240 V 208 V / 240 V 208 V / 240 V
AC voltage range at
208V
183V to 229V 183V to 229V 183V to 229V
AC voltage range at
240V
211V to 264V 211V to 264V 211V to 264V
Nominal AC current at
208V
25 A 32 A 32 A
Nominal AC current at
240V
25A 29.2A 32A
Maximum output cur-
rent at 208V
25A 32 A 32 A
Maximum output cur-
rent at 240V
25A 29.2 A 32 A
Total harmonic factor
of output current
<4% <4% <4%
Maximum residual out-
put current
30.4A 30.4 A 30.4A
Duration of the maxi-
mum residual output
current
250ms 250ms 250ms
Line synchronization
characteristics/inrush
current
Method 2/2.4A Method 2/2.4A Method 2/2.4A
Rated power frequency 60 Hz 60 Hz 60 Hz
Operating range at AC
power frequency
60Hz
59.3Hz to 60.5Hz 59.3Hz to 60.5Hz 59.3Hz to 60.5Hz
Output power at
+60°C (+140°F)
> 3300W >6700W >6700W
Power factor at rated
power
1 1 1