Installation Manual

Grid configurations 208V delta connection,
240V delta connection,
208V delta connection : 120V wye
connection,
240V : 120V split-phase system
Approvals and national standards, as per
03/2016
UL 1741, UL 1699B, IEEE 929-2000, IEEE
1547, Canadian Electrical Code® CSA C22.2
No. 107.1-01
10.6 Fan (only with Sunny Boy 7.0-US / 7.7-US)
Width x height x depth 60 mm x 60 mm x 25.4 mm
(2.36 in x 2.36 in x 1 in)
Noise emission, typical ≤45dB(A)
Maximum operating altitude 3000 m (9843 ft)
Air flow rate ≥40m³/h
10.7 Torques
Screw M5x60 for securing the inverter to the
wall mounting bracket
1.7Nm ± 0.3 Nm (15.05in-lb ± 2.65in-lb)
Screws for attaching the enclosure lid of the
Connection Unit
3Nm ± 0.3Nm (26.55in-lb ± 2.65in-lb)
Screws for grounding at equipment grounding
terminals
6Nm ± 0.3Nm (53.10in-lb ± 2.65in-lb)
Screws for AC-out connecting terminal plate for
AC connection
0.3Nm (2.65in-lb)
Screws for DC-in connecting terminal plate for
DC connection
0.3Nm (2.65in-lb)
Screws for SPS connecting terminal plate for
connecting the outlet for secure power supply
operation
0.3Nm (2.65in-lb)
10.8 Data Storage Capacity
Energy yields in the course of the day 63days
Daily yields 30 years
Event messages for users 1024 events
Event messages for installers 1024 events