Installation Manual

Position Designation
P Equipment grounding terminals for the equipment grounding conductors of the PV
array
Q Communication assembly
R
DISPLAY socket for connecting the display cable
6.3 AC Connection
6.3.1 Requirements for the AC Connection
Additionally required material (not included in the scope of delivery):
Conduits: 21mm (0.75in) or smaller with a proper reducing bush
Rain-tight conduit fittings for wet locations complying with UL 514B: 21mm (0.75in) or
smaller with a proper reducing bush
Requirements for the AC conductors:
The AC connecting terminal plate temperature rating is +90°C (+194°F).
The conductors with regards to its ampacity, rated temperatures, operating conditions and its
power loss must be made in accordance with the local standards and the National Electrical
Code
®
ANSI/NFPA 70 or the Canadian Electrical Code
®
CSA C22.1.
Conductor type: copper wire
Maximum permissible temperature for SB3.0-1SP-US-40, SB3.8-1SP-US-40, SB5.0-1SP-US
and SB6.0-1SP-US: +75°C (+167°F)
Maximum permissible temperature for SB7.0-1SP-US-40 and SB 7.7-1SP-US-40: +90°C
(+194°F)
The conductors must be made of solid wire, stranded wire or fine stranded wire. When using
fine stranded wire, bootlace ferrules must be used.
Conductor cross-section: 6mm² to 16mm² (10AWG to 6AWG)
Load-break switch an cable protection
Damage to the inverter due to the use of screw-type fuses as load-break switch
Screw-type fuses are not load-break switches.
Do not use screw-type fuses as load-break switches.
Use a load-break switch or a circuit breaker for load disconnection.
In PV systems with multiple inverters, protect each inverter with its own overcurrent protective
device. Observe the maximum permissible fuse protection (see Section10 "Technical Data",
page60). This will prevent residual voltage from being present at the corresponding cable
after disconnection.
The load-break switch or circuit breaker must be listed (see National Electrical Code
®
ANSI/
NFPA 70).
6 Electrical Connection
SMA Solar Technology America LLC
Installation ManualSB30-77-1SP-US-40-IA-xx-1328
ENGLISH