11 Troubleshooting
Problem Cause
Sunny View does not list the
NetID of your PV plant.
In your plant, no device is within the radio range of the
Sunny View.
Corrective measures:
Reduce the distance between the Sunny View and the plant
device.
Devices of your plant are not in operation.
Corrective measures:
Commission the devices.
The NetID 0 (Bluetooth off) is set for the devices.
Corrective measures:
Set the NetID of your plant for the devices.
Sunny View does not list all the
devices of your plant.
Sunny View completed the plant search before all devices were
connected to one another. For plants with many devices it may
take several minutes until all devices are connected to one
another.
Corrective measures:
Repeat plant search.
Not all devices are connected to one another. The wireless
connection of several devices may be disturbed by ambient
conditions.
Corrective measures:
Check the connection quality of the devices (see the
respective manual). The connection quality of all devices
must at least be "good".
Not all devices are connected to one another. In certain devices,
the NetID of your plant may not be set.
Corrective measures:
Make sure that the NetID of your plant is configured on the
devices.