Figure 1-4 Resistor Location in SWR Type Inverters
Mounting the Antenna
The antenna provided for use on the inverter comes with a PG type connector for mounting to
the underside of the inverter. The antenna will typically mount in the conduit hole provided for
communications cables.
The PG connector is a PG13.5 type. A PG16 type adapter has also been provided. Inspect the
communications conduit opening and determine if the opening will allow the PG16 adapter to
fit properly. Install the antenna by following the steps and referring to the following illustration.
Slide the seal-ring onto the antenna from the top, sliding it down the antenna to the base
until it is flush with the bottom of the antenna. Make sure the narrow end of the seal-ring
faces the base of the antenna.
Slide the pressure screw over the coax and over the seal ring until the small bumps on the
seal ring snap into the notches on the pressure screw.
Slide the threaded sleeve over the top and down the antenna and thread it onto the pres-
sure screw. Tighten the threaded sleeve until snug. Do not over tighten.
If required, slide the PG16 adapter over the coax and thread it onto the pressure screw.
Tighten the adapter until snug. Do not over tighten.
Route the coax through the opening on the underside of the inverter until the pressure
screw sits flush against the inverter