8. Reconnect the cables of the battery current sensor correctly as displayed in the graphic.
Make sure the lines have the correct polarity when doing this.
BatCur+ to terminal 1
BatCur– to terminal 2
9. Start the Sunny Island (see Section 9.1 "Switching On", page 73).
10. Check the current direction: "120.06 TotBatCur"
Current direction: Discharging the battery
No generator/grid connected
Loads are being supplied
The measured value of the battery current is positive.
Current direction: Charging the battery
Generator/grid connected
Loads not being/being marginally supplied
Battery is being charged
The measured value of the battery current is negative.