Product Overview
Monitron – Compact, easy to install for new or “standby” installations
Monitron combines the availability and dependability of electricity with the
comfort and performance of conventional hydronic heating using baseboard,
radiant or cast-iron radiators.
Monitron as a replacement unit: Works with virtually any existing
hot water hydronic radiation system. Although rated in kilowatts, it is
also clearly identified by BTU output.
Monitron as a standby unit: Particularly suitable for commercial
and industrial facilities, or office buildings which can’t risk down-time
with their existing heating equipment. If oil or gas is temporarily unavail-
able, the owner easily switches the heating system to the electric boiler.
Monitron as a primary heating unit offers:
• The convenience of electricity and the comfort of hydronics.
• No chimney required.
• Competitive pricing with electric baseboard systems.
• Simple zoning by zone valves.
Monitron by Slant/Fin is the electronic-age boiler designed to save
energy for new or existing heating systems.
America’s Best - Built Electric Boiler
• One piece cast-iron heat exchanger.
• Built in air eliminator.
• Internal baffles improve heat transfer.
TYPICAL WIRING DIAGRAM
TO ZONE VALVE
TRANSFORMER
WHEN USED
Monitron installed as primary boiler.
With manual mild-weather energy-saver switches *
Energy-saver
electric sequential control package
*
NORMAL OPERATIONS
When the thermostat calls for heat, the circulator turns on and the first
electric heater bank is energized. At preset 30-second intervals, the other
heater banks automatically energize. The circulator continues operating
until the room thermostat is satisfied. A flow switch supplied by Slant/Fin
or others is required. It prevents the elements from being energized
unless the circulator is operating. This avoids element burnout.
* All models except EH-8 and EH-10
OPTIONAL MILD-WEATHER OPERATION
Mild-weather energy savings are made possible through the use of
circuit breakers on the breaker panel. This permits the owner to man-
ually switch off one or more of the elements. Then, when just a mod-
erate amount of heat is needed, all the elements are not energized,
cycling is reduced, and overheating is diminished. This energy-saving
feature is standard on Monitron models EH-12-S through EH-40-S.
Standard equipment
• Dual limit aquastat
• Altitude pressure and temperature gauge
• Safety relief valve (unmounted)
• Circulator relay and heater contactors
• Circuit breaker (one or two heaters per breaker)
• Low voltage thermostat with adjustable heat anticipator
(packed separately)
• Drain cock,
3
⁄4 " (packed separately)
• Built-in air separator
• Cast-iron ASME approved heat exchanger
• Terminal blocks for circulator, thermostat, flow switch and
for zone valve transformer
• Sequencer
• Complete jacketing
• U.L. listed, ASME authorized
• Flow switch. Not included with, but necessary on all models
• Circuit breaker for circulator and control circuit.
• DOE 2012 compliant control.
MONITRON