4 EH-M3-40 Boiler Operation and Installation Instructions
Table 1. Lug Sizes
Table 2. Flow Switch Size Selection
* Straight pipe upstream and downstream of flow switch.
Model No.
Flow Switch
McDonnell & Miller No.
Pipe
Size
Minimum
Pipe Length*
EH-8-M3 thru EH-20-M3 FS4-3T3-1 1" 6-1/2”
Distribution Block
Grounding Lug
Neutral Lug
Wire Size Wire Size Wire Size
Model Phase CU-AL† CU-AL† CU-AL†
EH-8 thru 20 1 6-2/0 6-2/0 6-2/0
EH-12 thru 20 3 6-2/0 6-2/0 6-2/0
Neutral Lug Wire Size:For 3-wire single phase and 4-wire 3 phase
models equipped with circuit breakers. The neutral tap is for the
circulator and control transformer.
ALUMINUM conductors may be used, lug size, conduit size, ampacity and all
applicable codes permitting.
Table 3. Current Ratings
† Leg with the highest value of line current of an unbalanced 3-phase load.
‡ 125 VAC maximum rating of all hot conductors.
SINGLE PHASE 3 WIRE, 120/208V
Basic Model
No.
Heater Amperes
@ 208V
EH8-13-8-M3
EH10-13-8-M3
EH12-13-8-M3
EH16-13-8-M3
EH20-13-8-M3
29
36
43.4
58
72
SINGLE PHASE 3 WIRE, 120/240V
Basic Model
No.
Heater Amperes
@ 240V
EH8-13-4-M3
EH10-13-4-M3
EH12-13-4-M3
EH16-13-4-M3
EH20-13-4-M3
33
42
50
67
83
THREE PHASE 4 WIRE, 120/208V
WYE CIRCUIT ONLY
Basic Model
No.
Heater Amperes †
@ 208V
EH12-34-8-M3
EH16-34-8-M3
EH20-34-8-M3
43
58
72
THREE PHASE 4 WIRE, 120/240V
DELTA CIRCUIT ONLY
Basic Model
No.
Heater Amperes †
@ 240V
EH12-34-4-M3
EH16-34-4-M3
EH20-34-4-M3
50
67
83