User Guide
32
EM-40-SM Service Manual
Mode 8 – External DirectDrive Operation - Adjust Menu
Item Field Range Description Access Setting
1 to 8
MODE
Select the operating mode for the
control.
Factory
Installer
120 to 225°F
(49 to 107°C)
BOILER OUTLET MAXIMUM
Select the maximum boiler outlet
temperature. Exceeding this temperature
shuts off the burners.
Factory
OFF, 0:20 to
9:55 min, On
PUMP DELAY
Select the boiler pump purge time after
shutting off the burner.
Factory
°F or °C
TEMPERATURE UNITS
Select to display temperature in degrees
Fahrenheit or in degrees Celsius.
Factory
Installer
ADJUST MENU
After the last item, the control returns to the first item in the menu.
The Program menu items are the programmable settings
used to operate the system.
Press and hold all three
buttons simultaneously to enter the Program menu.
ItemItem
Change Value
Next ItemEnter Adjust Menu
Default
Setting 4