Ratings Chart
®
RATINGS CHART – COMMERCIAL BASEBOARD
MULTI/PAK 95
SLANT/FIN CORPORATION, Greenvale, NY 11548 • Phone: (516) 484-2600
FAX: (516) 484-5921 • In Canada: Slant/Fin LTD/LTEE, Mississauga, Ontario
www.slantfin.com
Cover
Type
Enclosure
Height
Element
Type
Tube Size
& Material
Fins
Per
Foot
Fin Size
& Material
Steam
1 PSI*
Btu/Hr.
Per Foot
HOT WATER RATINGS*
BTU/HR./FT. (Flow Rate 3 Ft./Sec.)
With or without dampers
110˚F 120˚F 130˚F 140˚F 150˚F 160˚F 170˚F 180˚F 190˚F 200˚F 210˚F 220˚F
S-532 1
1
⁄4" steel 4
1
⁄4" steel 32 1254 251 326 414 501 564 665 765 865 978 1078 1191 1317
S-540 1
1
⁄4" steel 4
1
⁄4" steel 40 1470 294 382 485 588 662 779 897 1014 1147 1264 1397 1544
95-10 9
3
⁄4” C-340
3
⁄4" copper 4
1
⁄4" alum. 40 1680 336 437 555 672 756 891 1025 1159 1311 1445 1597 1764
C-440 1" copper 4
1
⁄4" alum. 40 1780 356 463 587 712 801 943 1086 1228 1388 1531 1691 1869
C-540 1
1
⁄4" copper 4
1
⁄4" alum. 40 1745 349 454 576 698 785 925 1064 1204 1361 1501 1658 1832
S-532 1
1
⁄4" steel 4
1
⁄4" steel 32 1351 270 351 446 540 608 716 824 932 1054 1162 1283 1419
S-540 1
1
⁄4" steel 4
1
⁄4" steel 40 1577 315 410 520 631 710 836 962 1088 1230 1356 1498 1656
95-17 16
3
⁄4” C-340
3
⁄4" copper 4
1
⁄4" alum. 40 1840 368 478 607 736 828 976 1123 1270 1436 1582 1748 1933
C-440 1" copper 4
1
⁄4" alum. 40 1950 390 507 644 780 878 1034 1190 1346 1521 1677 1853 2048
C-540 1
1
⁄4" copper 4
1
⁄4" alum. 40 1911 382 497 630 764 860 1013 1166 1319 1491 1643 1815 2007
S-532 1
1
⁄4" steel 4
1
⁄4" steel 32 2153 431 560 710 861 969 1141 1313 1486 1679 1852 2045 2261
95-17 S-540 1
1
⁄4" steel 4
1
⁄4" steel 40 2390 478 622 789 956 1076 1267 1458 1649 1864 2055 2271 2510
Two-tier 16
3
⁄4” C-340
3
⁄4" copper 4
1
⁄4" alum. 40 2615 523 680 863 1046 1177 1386 1595 1804 2040 2249 2484 2746
element C-440 1" copper 4
1
⁄4" alum. 40 2770 554 720 914 1108 1247 1468 1690 1911 2161 2382 2632 2909
C-540 1
1
⁄4" copper 4
1
⁄4" alum. 40 2715 543 706 896 1086 1222 1439 1656 1873 2118 2335 2579 2851
* Based on 65˚F entering air temperature. Note: Ratings are based on active finned length (5-1/4" less than overall length).