User Guide

7
7
BEFORE OPERATING YOUR SUPERSKYE MACHINE FOR THE FIRST TIME READ THE
INSTRUCTION MANUAL THEN COMPLETE THE FOLLOWING PROCEDURES.
Your new EP6 must be prepared for use prior to any operation with refrigerant. Follow the
steps in the SET UP selection from MENU 3. This procedure can be used once at the time of
initial set up. It will be deactivated at completion of set up.
THE DEFAULT REFRIGERANT FOR SET UP IS R134a.
1. Fill the vacuum pump reservoir with 4 ounces of the oil provided by unscrewing the vent
cap/dipstick assembly and pouring it into the fill tube. Add an additional 4 ounces after the
motor starts in step 6 then replace the cap/dipstick assembly.
2. Determine which refrigerant you are going to use for the initial set up of the machine then
select the appropriate storage tank. Connect the appropriate short hoses to the tank and
machine (vapor to vapor/liquid to liquid), place the tank on the scale platform, open both
tank valves then connect the tank float lead.
3. Connect the machine to power and turn the master power switch ON. Select MENU 4 then
press the TANK SIZE button and select the tank size you are using (default is 30 lb.).
Return to MENU 4 and press the DISPLAY MODE button. The next screen allows you to
select your preferred weight (lbs & oz or Kg), pressure (PSI, KPa or mBAR) and
temperature (Fahrenheit or Celsius) measurements to be displayed. Press the desired
button for each option, select your desired measurement method then press the EXIT
button to return to the main option screen. Repeat as necessary to select your preferred
methods (default is lbs/oz, PSI and Fahrenheit). Once the measurement selection is
completed, press EXIT to return to the main menu. Press the MENU button to return to
MENU 3 and press the SET UP button.
a. If you are setting up for R134a, connect the tank hoses to the corresponding machine
and tank ports ( VAPOR to VAPOR/LIQUID to LIQUID ) and open both tank valves.
b. If you are setting up for R12, PRESS and HOLD the CHANGE GATE button and
move the access gate manually then connect the tank hoses to the corresponding
machine and tank ports ( VAPOR to VAPOR/LIQUID to LIQUID ) and open both tank
valves.
4. Press the CONTINUE button then press the R12 or R134a button on the following screen to
confirm the refrigerant selected. You have the option to move the gate again at this time.
DEFAULT SET UP IS R134a
PRESS AND HOLD CHANGE GATE
BUTTON TO MOVE GATE
DISPLAY
MODE
CHANGE
GATE
CONTINUE EXIT
CONFIRM GATE POSITION FOR
REFRIGERANT SELECTED