Owner`s manual
21
Indoor unit
Place of installation must have a good ventilation.
Indoor unit must be installed inside a house or building (cellar, veranda, service or technical room
etc.) on a dry place, where unit will be permanently protected against frost and where temperature
range of 7°C to 25° is kept, or on any other place which is clean, bright and has a good ventilation.
Place of installation should have a minimum volume (V
min
) according to the standard EN 378;
T1.V
min
=G/c, where G is a refrigerant charge in kg and c is an applicable limit value in kg/m
3
(for
refrigerant R407c the value of c is 0,31kg/m
3
). Minimum volume for the unit SHP-180IRC is 25,8m
3
.
It is prohibited to make any additional construction work, which could lead to the volume reduction or
any other modification, which could cause a change of temperature on indoor unit installation place.
If the unit is installed on a free accessible place, it is necessary to protect the unit by a suitable
securing covers.
As an installation place is recommended to select a place, where unit will not disturb surroundings by
its operation noise or by hot air.
The unit should be installed close to electric power supply.
Covers of the unit are made of painted steel, please protect these parts against humidity.
Upper side of the unit is made of plastics, please protect this part against heavy objects.
Please leave a sufficient space around the unit for maintenance and service work.