Service manual
48
Sponge(attachment)
Clamp(attachment)
Below 4mm
Clamp
Drain hose
Sponge (gray)
Drain stepup pipe note
◆
The install height of the drain raising pipe should less than 280mm.
◆
The drain raising pipe should form a right angle with the unit, and distance to unit should not beyond 300mm.
Instruction
◆
The slant gradient of the attached drain hose should be within 75mm so that the drain hole doesn’t has to endure
the unnecessary outside force.
◆
Please install the drain hose according to the following process if several drain hoses join together.
b. Check the smoothness of drain after installation.
◆
Check the drain state by immitting 600cc water slowly from the outlet vent or test hole.
◆
Check the drain in the state of refrigerating after installation of the electric circuit.
46