Service manual
8
PRODUCT
Model
Heat pump MC-D21AI MC-D24AI
Product Code CN210N0040 CN210N0050
Capacity
Cooling kW 6.0 7.1
Heating kW 6.60 8.00
Power supply V-Ph-Hz 220~2400-1-50 220~2400-1-50
Motor power input kW 0.11 0.11
Air ow volume
m
3
/h 1000 1000
CFM 589 589
Sound pressure level(H/L) dB(A) 42/34 42/34
Fan motor
Output kW 0.061 0.061
Running current A 0.588 0.588
Connecting pipe
Gas inch 5/8″(15.9mm) 5/8″(15.9mm)
Liquid inch 3/8″(9.52mm) 3/8″(9.52mm)
Connection method Flare Connection Flare Connection
Drain pipe
External dia. mm Φ20 Φ20
Thickness mm 1.5 1.5
Outline dimension W×D×H mm 1100×200×615 1100×200×615
Package dimension W×D×H mm 1323×305×743 1323×305×743
Net Weight kg 31 31
Gross weight kg 41 41
Loading quantity
20'GP 72 72
40' GP 162 162
40' HQ 162 162
Notes:
a. The rated cooling capacity data is measured under the following work condition: Indoor Temperature is 27
℃
DB,
1 9
℃
WB. Outdoor Temperature is 35
℃
DB.The rated heating capacity data is measured under the following work
condition: Indoor Temperature is 20
℃
DB. Outdoor Temperature is 7
℃
DB, 6
℃
WB.
b. The data will change with the change of products. Refer to those parameters listed on nameplate.
c. Noise was tested in semi-silenced room, so the actual noise value will be a little higher for change of ambient.
7