SERVICE MANUAL MULTI COMBI OUTDOOR AND INDOOR UNITS CASSETTE, FLOOR&CEILING, DUCT UNITS OUTDOOR UNITS (36k,42k)
COMBINATION TABLE (unit: kW) MC-E18AI 1 model 2 models 2,1 2,1+2,1 MC-E24AI 2 models 3 models 2,1+2,1 2,1+2,1+2,1 2 models 2,1+2,1 MC-E28AI 3 models 2,1+2,1+2,1 4 models 2,1+2,1+2,1+2,1 2,1+2,1 2,6+7,1 2,1+2,1+2,1 MC-E36AI 3 models 2,1+3,5+5,0 2,6+3,5+5,0 2,1+2,1+2,1+2,1 4 models 2,1+2,1+5,0+5,0 2,6+2,6+2,6+2,6 2 models 2,6 2,1+3,5 2,1+3,5 2,1+2,1+5,0 2,1+3,5 2,1+2,1+5,0 2,1+2,1+2,1+5,0 2,1+2,6 3,5+3,5 2,1+2,1+2,6 2,1+3,5+7,1 2,6+3,5+7,1 2,1+2,1+2,1+2,6 2,1+2,6+2,6+2,6 2,6+2,6+2
MC-C12AI unit low fan motor speed (RPM) air flow volume (m3/h) noise level dB(A) 620 450 42 mid 720 500 44 MC-C18AI High 820 low 620 mid 720 600 46 450 42 500 44 Model of Outdoor Unit max Cooling capacity* (W) nom min max Total power input in cooling mode* (W) nom min EER* (nominal) max Heating capacity* (W) nom min max Total power input in heating mode* (W) nom min COP* (nominal) MC-C24AI High 820 600 46 MC‐E36AI MC‐E42AI 10000 9790 2100 4300 3030 1300 3,23 12000 11000 2600 4140
PRODUCT 1 MODELS LIST 1.1 Outdoor Unit Capacity Units Series Model MC-E36AI Product Code Cooling (kW) Heating (kW) CN860W0011 9.789 11 Outdoor Unit MC-E42AI CN860W0020 11.6 Ref. Power Supply R410A 220~ 240V-1Ph-50Hz Appearance 13 1.2 Indoor Unit 1.2.1 Duct type Units Series Duct Type Indoor Unit Capacity Model Product Code Cooling (kW) Heating (kW) MC-D09AI CN210N0010 2.5 2.80 MC-D12AI CN210N0020 3.5 3.85 MC-D18AI CN210N0030 5.0 5.50 MC-D21AI CN210N0040 6.0 6.
1.2.3 Floor ceiling type Units Series Floor/ Ceiling Type Indoor Unit Capacity Model Product Code Cooling (kW) Heating (kW) MC-F09AI CN610N0010 2.5 2.80 MC-F12AI CN610N0020 3.5 3.85 MC-F18AI CN610N0030 5.0 5.50 MC-F18AI CN610N0040 7.1 8.00 Ref. Power Supply R410A 220~ 240V -1Ph-50Hz Appearance 1.2.2 Cassette type Units Series Cassette Type Indoor Unit Capacity Model Product Code Cooling (kW) Heating (kW) Ref. Power Supply MC-C24AI CN510N0030 7.1 8.
2 NOMENCLATURE MC - E 09 A I 1 2 3 4 5 6 NO. Description 1 MC 2 - Options Multi combi serie E-outdoor unit H- wall mounted unit D- duct unit C- cassette unit F- floor ceiling unit 3 Type of unit 4 Capacity 0.
3 FUNCTION Function For Comfortable Air Conditioning For Flexible Control Duct type Cassette type Floor ceiling type Fan operation Mode ● ● ● Auto Swing Controller - ● ● Timer Selector ● ● ● Auto Mode Operation ● ● ● Cool Mode Operation ● ● ● Heat Mode Operation ● ● ● Dry Mode Operation ● ● ● Fan Mode Operation ● ● ● Sleep mode setting ● ● ● Drain Pump ● ● - Wired Controller ● ● ● Wireless Controller ● ● ● ●:Have Functions - :No Functions PIPE DIAMETER
Model Capacity Cooling Heating Rated current2 Refrigerant Compressor MC‐E42AI 9.789 11.6 kW 11 13 220‐240/1/50 220‐240/1/50 Cooling kW 3.030 3.590 Heating kW 3.010 3.545 Cooling A 13.87 16.43 Heating A Type 13.78 16.22 R410A R410A 3.6 4.8 Charge volume kg Brand - MITSUBISHI MITSUBISHI Model - TNB220FLHMC TNB306FPGM Type - Inverter Scroll Inverter Scroll Quantity - 1 1 Power Input W 2200.00 3010.00 Rated Load Amp (RLA) A 9.70 13.
4 PRODUCT DATA 4.1 Product data of outdoor Model Heat pump MC-E36AI MC-E42AI Product Code CN860W0010/CN860W0011 CN860W0020 Cooling kW 9.789 11.6 Heating kW 11 13 Capacity adjustment range % 23% ~ 150% 19%~ 150% EER kW/kW 3.23 3.23 COP kW/kW 3.65 3.67 Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 R410a R410a 3.6 4.
4.2 Product data of indoor 4.2.1 Duct Type Model Heat pump MC-D09AI MC-D12AI MC-D18AI Product Code CN210N0010 CN210N0020 CN210N0030 Cooling kW 2.5 3.5 5.0 Heating kW 2.80 3.85 5.50 Power supply V-Ph-Hz 220 ~ 240-1- 50 220 ~ 240-1- 50 220 ~ 240-1- 50 Motor power input kW 0.075 0.065 0.08 3 m /h 450 550 700 CFM 265 324 412 dB(A) 37/31 39/32 40/33 Output kW 0.041 0.036 0.044 Running current A 0.406 0.348 0.428 Gas inch 3/8″(9.52mm) 3/8”(9.52mm) 1/2″(12.
Model Heat pump MC-D21AI MC-D24AI Product Code CN210N0040 CN210N0050 Cooling kW 6.0 7.1 Heating kW 6.60 8.00 Power supply V-Ph-Hz 220~2400-1-50 220~2400-1-50 Motor power input kW 0.11 0.11 m3/h 1000 1000 CFM 589 589 dB(A) 42/34 42/34 Output kW 0.061 0.061 Running current A 0.588 0.588 Gas inch 5/8″(15.9mm) 5/8″(15.9mm) Liquid inch 3/8″(9.52mm) 3/8″(9.
4.2.2 Cassette type Model Heat pump MC-C12AI MC-C18AI MC-C24AI Product Code CN510N0040 CN510N0050 CN510N0030 Cooling kW 3.5 4.5 7.1 Heating kW 4.0 5.0 8 Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 220~240-1-50 Motor power input kW 0.05 0.05 0.1 3 m /h 600 600 1180 CFM 353 353 694 dB(A) 46 46 39/35 Output kW 0.011 0.011 0.055 Running current A 0.25 0.25 0.535 Gas inch 3/8″(9.52mm) 1/2″(12.7mm) 5/8″(15.9mm) Liquid inch 1/4″(6.35mm) 1/4″(6.
4.2.3 Floor ceiling type Model Heat pump MC-F09AI MC-F12AI Product Code CN610N0010 CN610N0020 Cooling kW 2.5 3.5 Heating kW 2.8 3.85 Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 Motor power input kW 0.055 0.055 3 m /h 650.0 650.0 CFM 383.0 383.0 dB(A) 40/36 40/36 Output kW 0.3 0.3 Running current A 0.297 0.297 Gas inch 3/8″(9.52mm) 3/8”(9.52mm) Liquid inch 1/4″(6.35mm) 1/4″(6.
Heat pump MC-F18AI MC-F24AI Product Code CN610N0030 CN610N0040 Model Cooling kW 5 7.1 Heating kW 5.5 8.0 Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 Motor power input kW 0.11 0.11 3 m /h 950 1250 CFM 559 736 dB(A) 45/40 48/40 Output kW 0.061 0.061 Running current A 0.588 0.
5 PIPING DIAGRAM Schematic Diagram of MULTI COMBI M The outdoor and indoor units start to work once the power is switched on. During the cooling operation, the low temperature, low pressure refrigerant gas from the heat exchanger of each indoor unit gets together and then is taken into the compressor to be compressed into high temperature, high pressure gas, which will soon go to the heat exchanger of the outdoor unit to exchange heat with the outdoor air and then is turned into refrigerant liquid.
CONTROL
CONTROL 1 OPERATION FLOWCHART Conn ecting To Power Supply Initialization Of Bectronic Expansion Valve Volume:.
1.
1.
2 MAIN LOGIC 2.1 Control Function of Outdoor Unit 2.1.1 Cooling Mode a. Cooling conditions and process: If the compressor is in stop status and start the unit for cooling operation, when one of the indoor units reaches the cooling operation condition, the unit start cooling operation; in this case, the electronic expansion valve, the outdoor fan and the compressor start operation. b. Stop in cooling operation a) Compressor stops The compressor stops gradually, the outdoor fan stops after 1min.
The indoor unit displays “H1” c) Oil-returned finished condition in heating mode The duration reaches 5min 2.1.4 Fan Mode The compressor, the outdoor fan and the 4-way valve are closed; temperature setting range is 16 ~ 30℃ . 2.2 Protection Function 2.2.1 Mode Conflict Protection of indoor unit When the setting mode is different of different indoor unit, the unit runs in below status: a.
b) On condition that a low pressure protection error occurs and the whole unit has stopped for more than three minutes and it is detected continuously for six seconds that the low pressure protection switch is closed, then this error can be eliminated. However, if the low pressure protection occurs twice in one hour, then it has to eliminate the error by powering the outdoor unit again. 2.2.
b) The defrosting symbol “H1” will be displayed when the defrosting signal is received from the outdoor unit. e. AUTO Mode a) When the ambient temperature is higher than 25℃ , the unit will run as the COOL mode. b) For the cooling and heating unit, if the ambient temperature is or lower than2 0℃ (72 ℉ ), the unit will run as the HEAT mode.
Temperature 30 29 27 26 ( ) 28 ℃ / 31 25 24 23 22 21 20 19 18 17 16 0 1 2 3 4 5 6 7 8 9 10 11 12 Time/(Hour) Temperature Sleep Curve under the HEAT mode 31 ) / ℃ ( 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 0 1 2 3 4 5 6 7 8 9 10 11 12 Time/(Hour) d) Sleep 3 (Self-Defined Sleep Mode) How to set the sleep 3 curve: 1)When the sleep 3 mode is selected, press the “Timer” button to go to the setting status with “1 Hour” displayed and the corresponding temperature of the sle
e. Quiet Quite Function: It is divided into the “Quiet” mode and “Auto Quiet” mode. a) Under the “Quiet” mode, the low fan speed will be kept and is unchangeable. b) Under the “Auto Quiet” mode, the fan speed changes in accordance with the difference of the indoor ambient temperature and the set temperature. f. Timer a)Timer On When the unit is powered on but in the idle condition, it is available to set when to start the unit. Then, when the unit starts, it will run as the previously set mod.
a)For the duct type indoor unit: Under the COOL, HEAT, DRY, or FAN mode, the return air temperature sensor is adopted; while under the HEAT mode, it is the receiver temperature sensor. For the cassette type, floor/ceiling type indoor unit: Under all modes, the return air temperature sensor is adopted.
3 REMOTE CONTROLLER 3.1 Wired Remote Controller 3.1.1 Wired Controller XK19 It is optional for the cassette type, wall-mounted, and floor ceiling indoor units.
No. Symbols Description 1 Swing function. 2 Sleep function (3 types: sleep 1,sleep2 and sleep 3). 3 Running modes of the indoor unit (Cooling, Dry, Fan and Heating). 4 Defrosting function for the outdoor unit. 5 Gate-control function (this function is yet unavailable for this unit). 6 Lock function. 7 High, middle, low or auto fan speed of the indoor unit. 8 SHIELD Shield functions (buttons, temperature, On/Off, Mode or Save is shielded or Save is shielded by the remote monitor.
Function of the Buttons No. Name Function 1 Enter/cancel 2 ▲ 6 ▼ ① Running temperature setting of the indoor unit, range:16 ~ 30℃ . ② Timer setting, range:0.5-24 hr. ③ Switchover between quiet/auto quiet or among sleep1/sleep2/sleep 3. 3 Fan Setting of the high/middle/low/auto fan speed. 4 Mode 5 Function 7 Timer Timer setting. 8 On/Off Turn on/off the indoor unit.
◆ Sleep Setting Sleep on: Press Function under on state of the unit till the unit enters the Sleep setting interface. Then press ▲or ▼ to switch among Sleep 1, Sleep 2 and Sleep 3. After that, press Enter/cancel to confirm the setting. Sleep off: When the Sleep function is activated, press Function to enter the Sleep setting interface. After that, press Enter/cancel to can this function.
Save Setting for Heating: Under on state or in the Heating mode of the unit, press Function to enter the Save setting interface and then press ▲or ▼ to adjust upper limited value in the Heating mode. After that, press Enter/Cancel to activate the Save function for heating. The upper initial limited value in the Heating mode is 20℃ . After the Saving function is activated, press Function to enter the Save setting interface and then press Enter/Cancel to cancel this function. Notes: a.
Memory recovery: If this function has been set for the wired controller, the wired controller after power failure will resume its original running state upon power recovery. Memory contents: On/Off, Mode, set temperature, set fan speed, Save function and Lock function. 3) Enquiry of the Outdoor Ambient Temperature Under the “On” or “Off” state of the unit, press Enter/Cancel for 5s, and the outdoor ambient temperature will be displayed after a sound of click.
3.2 Wireless Remote Controller Wireless Remote Controller YT1F Notes: a. Be sure that there are no obstructions between the receiver and the remote controller; b. Do not drop or throw the remote controller; c. Do not let any liquid into the remote controller and expose the remote controller to direct sunlight or any place where is very hot. d. This is a general use remote controller. If press some button which is not available for the corresponding function, the unit will keep the original running status.
is displayed, the current time is the Clock value; otherwise it is the Timer value. ◆ LIGHT Light On and Light Off can be set by pressing this button when the unit is at On or Off status. After powered on, the default is Light On. ◆ TURBO In Cool or Heat mode, pressing this button can activate or deactivate this function. When this function is on, its symbol will be displayed. Any change of either mode or fan speed will make this function canceled automatically.
the main unit will close automatically). 2) Press MODE to select the desired running mode. 3) Press + or - to set the desired temperature (it is unnecessary to set the temperature under the AUTO mode.) 4) Press FAN to set the fan speed, AUTO, LOW, MID, or HIGH. 5) Press to select the swing angle. 3.2.3 Guide for Optional Operation ◆ About BLOW This function indicates that moisture in the evaporator of the indoor unit will be dried after the unit is stopped to avoid mould. a.
INSTALLATION 34
INSTALLATION 1 PRECAUTIONS FOR INSTALLATION 1.1 Precautions for Installation Before installation, please ensure if the installing site, power ratings, possible operating range (pipe distance, height difference between indoor and outdoor unit, power voltage) and installing space are correct and suitable. The outdoor unit is general to all models according to its power. ◆ To ensure correct installation, please make sure to read the Safety Considerations thoroughly before starting the installation works.
1.2 Key Points of Installation Installation Procedures Description and Acceptance Criteria Material Selection and Equipment Inspection The materials specified on the engineering drawing shall be purchased as specified (e.g. copper tube, thermal insulation tube, PVC pipe, power cables, air switch, etc). The materials not specified on the engineering drawing shall be purchased according to the actual quantity of works (e.g. hanger frame, cable duct, etc).
2 FLOW CHART OF INSTALLATION Design Kicking-off Material selection Inspection of site installation position Installation of connection pipes Installation of indoor unit Installation of remote control Connection of power cables and communication wires Installation of drainage pipes Purge and make leakage detection under pressure Installation of outdoor unit Connection of power cables Thermal insulation Connection of indoor unit and outdoor unit Connection of indoor unit and outdoor unit Leakage
3 OUTDOOR UNIT INSTALLATION 3.1 Before Installation ◆ Check if there is any damage to the unit when receive and unpack the unit, and check if the compressor runs reversely, if the grease oil and refrigerant leak, and if all parts are completely prepared. If there is any damage on the surface or the inner side, please inform the shipping company or the equipment manufacturer in the written form promptly.
350 840 412 110 76 340 378 1022 950 192 96 572 The following figure is applicable to the Outdoor units of :MC-E42AI 450 191 99 631 362 121 76 440 401 1103 1087 1015 3.
4 INDOOR UNIT INSTALLATION 4.1 Installation of Duct Type 4.1.1 Before Installation Check if there is any damage to the indoor unit, and the wireless controller and other part and components are prepared completely. 4.1.2 Installation Site ● The selection of the installation place of the air conditioner unit The installation must accord with the national and local safe criterion.
Table Outline Dimensions: Item Model MC-D09AI MC-D12AI MC-D18AI MC-D21AI MC-D24AI A B C D E F G H I J 742 491 662 620 700 615 782 156 200 635 942 491 862 820 900 615 982 156 200 635 1142 491 1062 1020 1100 615 1182 156 200 635 4.1.5 Installation Clearance Data Nut with washer Spring pad >500 >250 a. Installation of the Indoor Unit Insert the M10 expansion bolt into the hole, and then knock the nail into the bolt.
Hanger bolt Air conditioning unit Anchor Install the indoor unit on the ceiling: CAUTION: a. Prior to the installation, please make a good preparation for all piping (refrigerant pipe, drain pipe) and wiring (wires of the wired controller, wires between the indoor and outdoor unit) of the indoor unit to make the further installation much easier. b. If there is an opening in the ceiling, it is better to reinforce it to keep it flat and prevent it vibrating. Consult the user and builder for more details.
Table No. Name No. Name 1 Hanger 5 Filter Screen 2 Return Air Duct 6 Main Air Supply Duct 3 Canvas Duct 7 Air Supply Outlet 4 Return Air Inlet 8 Plenum Box b. Installation of the Round Air Supply Duct 1 2 3 4 5 6 7 8 9 Table No. Name No. Name 1 Hanger 6 Transition Duct 2 Return Air Duct 7 Air Supply Duct 3 Canvas Duct 8 Diffuser 4 Return Air Louver 9 Diffuser Joint 5 Air Supply Outlet c.
f. Make sure that there are enough space for care and maintenance. Make sure that the weight between the indoor unit and ground is above 1800mm. g. When installing the steeve bolt, check if the install place can stand the weight 4 times of the unit’s. If not, reinforce before installation.
650 570 400 570 604 650 Install dimension of mode MC-C12AI, MC-C18AI ◆ The drilling of holes in the ceiling must be done by the professional personnel. (160) Installation stands for main body of the unit Ceiling Above 20 Notes: The dimension for the ceiling openings with * marks can be as large as 910mm. But the overlapping sections of the ceiling and the decorated surface boards should be maintained at no less than 20mm. 2.2.
MC-C12AI, MC-C18AI H >20 Wall surface Wall surface Wall surface ≥1500 ≥1800 ≥1500 Model MC-C12AI MC-C18AI unit:mm H 260 Ground surface ★ Main body of hoisting air conditioner a. The primary step for install the indoor unit. ◆ When attach the hoisting stand on hoisting screw, do use nut and gasket individually at the upper and lower of the hoisting stand to fix it. The use of gasket anchor board can prevent gasket break off. b.
◆ When connect, smear both inside and outside of the flare nut with freeze motor oil, screw it by hand and then tighten it with spanner. ◆ Refer to form 1 to check if the wrench had been tightened (too tight would mangle the nut and lead leakage). ◆ Examine the connection pipe to see if it had gas leakage, then take the treatment of heat insulation, as shown in the fig.5. ◆ Only use median sponge to entwine the wiring interface of the gas pipe and heat preservation sheath of the gas collection tube.
Sponge(attachment) Clamp Sponge (gray) Clamp(attachment) Drain hose Below 4mm Drain stepup pipe note ◆ The install height of the drain raising pipe should less than 280mm. ◆ The drain raising pipe should form a right angle with the unit, and distance to unit should not beyond 300mm. Instruction ◆ The slant gradient of the attached drain hose should be within 75mm so that the drain hole doesn’t has to endure the unnecessary outside force.
4.3 Installation of Floor Ceiling Type 4.3.1 Before Installation Check if there is any damage to the indoor unit, and the wireless controller and other part and components are prepared completely. 4.3.2 Installation Site Selection of Installation Location for Air Conditioner Unit The installation of air conditioner unit must be in accordance with national and local safety codes. Installation quality will directly affect the normal use of air conditioner unit.
b. Important Notice ◆ The unit must be installed by the professional personnel according to this install instruction to ensure the well use. Please contact the local Sinclair special nominated repair department before installation. Any malfunction caused by the unit that is installed by the department that is not special nominated by Sinclair would not deal with on time by the inconvenience of the business contact.
bracket when it is outside the arrowed position. (Refer to ⑤ ) ◆ Suspension bolt stays inside the cap of indoor unit. Never remove the cap. 5) Lift the unit and slide forward unit the dent. (Refer to ⑥ ) 6) Screw tightly both hanger bracket-setting bolts (M8). (Refer to ④ ) 7) Screw tightly both hanger bracket-fixing bolts (M6) to prevent the movement of the indoor unit. (Refer to ④ ) 8) Adjust the height so that rear side of the drainpipe slightly inclines to improve drainage.
5 REFRIGERATION PIPING WORK 5.1 Connection between Indoor and Outdoor Units a. Wiring of the Power Cord CAUTION ! A breaker must be installed, capable of cutting off the power supply for the whole system. 1) Open the side plate. 2) Let the power cord go through the rubber ring. 3) Connect the power card to the terminals “L”, “N” and also the earthing bolt, and then connect the wiring terminals “N(1),2,3” of the indoor unit to those of the outdoor unit correspondingly. 4) Fix the power cord with wire clips.
Flare Nut Pipe Pipe Torque Wrench Ordinary 4) The bending degree of the pipe can not be too small; otherwise it will crack. And please use a pipe bender to bend the pipe. 5) Wrap the exposed refrigerant pipe and the joints by sponge and then tighten them with the plastic tape. Moments of Torque for Tightening Screws Diameter Wall Thickness(mm) Moment of Torque φ6.35mm ≥ 0.5 15-30(N·m) φ9.52mm ≥ 0.71 30-40(N·m) φ12.7mm ≥1 45-50(N·m) φ15.9mm ≥1 60-65(N·m) CAUTION ! a.
5.2 Refrigerant Charging and Trial Running a. Refrigerant Charging 1) The refrigerant has been charged into the outdoor unit before shipment, while additional refrigerant still need be charged into the refrigerant pipe during the field installation. 2) Check if the liquid valve and the gas valve of the outdoor unit are closed fully. 3) As shown in the following figure, expel the gas inside the indoor unit and refrigerant pipe out by the vacuum pump.
Serial No. Model Indoor Unit ⑤ Ducted Type MC-D09AI Indoor Unit ④ Ducted Type MC-D09AI Indoor Unit ③ Ducted Type MC-D09A Indoor Unit ② Ducted Type MC-D09AI Indoor Unit ① Ducted Type MC-D18AI Liquid Refrigerant Pipe Serial No. e d c b a Diameter φ6.35 φ6.35 φ6.35 φ6.35 φ9.52 Length 20m 20m 15m 5m 5m The total length of each liquid refrigerant pipe is: e+d+c+b+a=20+20+15+5+5=65m. Thus, the minimum additional refrigerant charge=(65-50)×0.022=0.
d. Trial Running 1) Check before the Trial Running ◆ Check if the appearance of the unit and the piping system are damaged during the transportation. ◆ Check if the wiring terminals of the electronic component are secure. ◆ Check if the rotation direction of the fan motor is right. ◆ Check if all valves in the system are fully opened. 2) Trial Running ◆ The trial running should be carried out by the professionally skilled personnel on the premise that all items listed above are in normal conditions.
6 ELECTRIC WIRING WORK 6.1 Wiring Principle 6.1.1 Itemized Description of Cautions. The electrical installation must be done by professional electricians. The electrical installation must be done in accordance with applicable technical codes and other rules. WARNING! Please make sure to install earth leakage circuit breaker. Earth leakage circuit breaker must be installed to prevent electric shock or fire. CAUTIONS! The air conditioner must be securely earthed.
Clamp them with the corresponding wire clamp packed in the chassis; e. Reassemble the electrical box cover. f. Recover the surface panel. g. The temperature of refrigerant circuit will be high, please keep the interconnection cable away from the copper tube.
1) The air conditioning unit should be installed where ventilation is in good condition, otherwise the working capability of the unit would be reduced or working noise would be increased. 2) The air conditioning unit should be installed on the base frame which is stable and secure uncouth to withstand the weight of the unit; otherwise it would incur vibration and noise.
MAINTENANCE 60
MAINTENANCE 1 TROUBLE TABLE WARNING ! a. In the event of abnormal conditions (like, stinky smell), please shut off the main power supply immediately and then contact the SINCLAIR appointed service center; otherwise the continuous abnormal running would damage the air conditioning unit and also would cause electric shock or fire hazard etc. b.
1.3 Error description If some error occurs when the unit is running, the error code will be displayed on the wired controller and the main board of the outdoor unit.See the table before for more details about the meaning of each error.
The drilling of ? cooling/heating Min. (capability test code) Quick IPLV must test be done by the professional / holes in Cooling the ceiling personnel. flash P0 Cooling IPLV test Cooling level AA performance test Mid.
Short/open circuit of the temperature sensor at the inlet of the condenser coil ( for the commercial unit) / A5 / / / / / Short/open circuit of the temperature sensor at the outlet of the condenser coil ( for the commercial unit) / A7 / / / / / Memory card error / EE / / / / / Frequency limitation/ degradation for module circuit protection (for phase circuit) / En / / / / / Frequency limitation/ degradation for module temperature protection / EU / / / / / Frequency li
43 Unit D indoor unit pipe outlet temperature sensor error 51 Unit E communication error 56 Unit E mode conflict 44 Unit D indoor pipe inlet temperature sensor error 52 Unit E indoor pipe midway temperature sensor error 57 Unit E anti-freezing protection 45 Unit D indoor ambient temperature sensor error 53 Unit E indoor unit pipe outlet temperature sensor error C5 Jumper terminal error Error description of outdoor refrigerant pipe detection function Wiring error or component error Unit w
2 FLOW CHART OF TROUBLESHOOTING Service personnel shall collect the malfunction information as much as possible and research them thoroughly, list these electrical parts which may cause malfunction, service personnel shall be able to determine the specific reason and solve the faulted parts.
◆ Malfunction display: E3 Compressor Low Pressure Protection Compressor Low Pressure Protection Y Check if the pressure is really low pressure with the measurement of a manometer N Refer to the high pressure protection Y Check if refrigerant in the system is insufficient N Charge refrigerant according to the amount specified in the nameplate and calculated additional amount Y Check if operation mode of indoor unit is properly set N Refer to Instruction Manual of indoor unit Y Check if gas valve
◆ Malfunction display: E4 Compressor Exhaust High Temperature Protection Discharge temperature protection Y Measure if compressor’s discharge temperature has reached115 N Measure if temperature sensor’s resistance value is correct Y N Replace relevant discharge temperature sensor Y System pipeline leaks so complementation is needed.
◆ Malfunction display: E9 Full Water Protection Full Water Protection Y N Check if water overflow Check if the voltage of liquid level switch end is ok Y Check if the water drainage works pump N Check if the voltage of water drainage pump end is ok N Replace the main board of the indoor uint Y Check the liquid level switch N Replace the main board of the indoor uint Y Y Check if the water drainage pipe is jammed or if water flows smoothly N Check the cables of water drainge pump Adjust t
◆ Malfunction display: F3 Failure of Outdoor Ambient Sensor Failure of outdoor Ambient sensor Y Check if the plug of the temperature sensor is correctly connected with socket on the mainboard N Check the direction of the plug and socket Y N Remove the sensor to check if the resistance value is ok Replace temperature sensor Y Replace mainboard of the indoor uint ◆ Malfunction display: F5 Failure of Exhaust Temp. Sensor Failure of Exhaust Temp.
3 WIRING DIADRAM 3.
3.2 Indoor unit 3.2.1Duct type 3.2.
MC-12AI, MC-C18AI 3.2.
4 DISASSEMBLY AND ASSEMBLY PROCEDURE OF MAIN PARTS 4.1 Outdoor Unit Side Discharge Indoor Unit Assembly and Disassembly of the Compressor Remarks: Prior to the assembly of the compressor, make sure there is no refrigerant in the pipeline and the power supply is cut off. Steps 1.Remove the power cords away Illustrations Operation Instructions Label the color of the power cords and the code of the terminals ●Loosen the screws used to fix the power cord with a screw driver. ●Pull out the power cord.
6.Connect the pipeline with the suction and discharge ports of the compressor Reconnect the pipeline to the compressor as the same as the previous status. Label the color of the power cords and the code of the terminals 7. Reconnect the power cord ●Burn the joint of the connecting pipe and then connect the pipeline wit the compressor. Note: never let the flame touch any other component. ● Tight the screws used to fix the power cord with a screwdriver. ●Reconnect the power cord.
4.2 Indoor Unit 4.2.1Duct type Assembly and Disassembly of the Electric Fan Remarks: Prior to the assembly and disassembly, make sure the power supply is cut off. Steps 76 Illustrations Operation Instructions 1.Pull out the electric wire of the motor. ● Cut off the power supply of the indoor unit, open the cover plate of the electric box and then pull out the electric wire inside the box. 2.Remove the cover plate for return air.
4.2.2 Cassette type Removal and Assembly of Fan Motor Step Illustration Handling Instruction 1. Loosen the screws fixing the water tray ●Use screwdriver to loosen the screws fixing the water tray 2. Remove the water tray ●Remove the water tray 3. Loosen the bolts fixing the fan ●Use spanner to loosen the bolts fixing the fan. 4. Remove the fan ●Remove the fan 5. Loosen the screws fixing the motor ●Use screwdriver to loosen the screws fixing the motor 6.
9. Mount the water tray and tighten the screws ●Use screwdriver to loosen the screws fixing the water tray emoval and Installation of Drainage Pump Step Illustration Handling Instruction Loosen these screws 1. Loosen the screws fixing the water tray ●Use screwdriver to loosen the screws fixing the water tray 2. Remove the water tray ●Remove the water pump and replace it. 1.Loosen these screws 3. Pull out the water outlet pipe and loosen the screws fixing the water pump. 2.
4.2.3 Floor ceiling type Remove panel grating module Remark: Make sure that the power supply is cut off before disassembling and protect all the parts during disassembly. Do not put filter screen near the high temperature heat source. Step Illustration Handling Instruction ●Move down the clip of the sub-assy of fromt grill until the front grill is open. (As is Remove sub-assy of shown in the graph, arrow front grill represents the position of bottons. There are two clips for each grating.
Remove panel parts Remark: Make sure the power supply is cut off before disassembling and protect all the parts during disassembly. Do not scratch the outer parts. Step Illustration Handling Instruction ●Remove the screws shown by the arrow in the graph with screwdriver (two on both right and left and 4 in the front) and then remove the panel parts.
Remove water-containing plate modules Remark: Make sure the power supply is cut off before disassembling and protect all the parts during disassembly. Step Illustration Remove watercontaining plate modules Handling Instruction ●Remove the watercontaining plate modules. Remove evaporator components Remark: Make sure that the power supply is cut off and protect the copper tube and aluminum fin. If the time for disassembly shall be long, seal the copper tube.
Remove fan and motor components Remark: Make sure that the power supply is cut off before disassembling and protect all the parts during disassembly, especially the fastening screws for fans. Step 82 Illustration Handling Instruction 1. Remove front and back scroll cases ●Press the buckle at the joints of front and back scroll cases with hands and pull upward to remove the front scroll case. Then remove the screws on the back scroll case. Lift the buckle of back scroll case with hands and remove it.
PARTS GUIDE MULTI COMBI OUTDOOR AND INDOOR UNITS CASSETTE, FLOOR&CEILING, DUCT UNITS OUTDOOR UNITS
Exploded view of model: MC-D09AI, MC-D12AI 84
No Description Part Code Note Qty Price Code MODEL: MC-D09AI, MC-D12AI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 Air outlet frame assy Cover of Air Outlet Water Tray Assy Top Cover Assy Evaporator Assy Sealplate sub-assy (evaporator) Left Side Plate Assy Seal of Letout Pipe Assy Front volute casing Rear volute casing Centrifugal fan Transformer 48X26G Terminal Board Main Board Z6325L Capacitor CBB61 1.
Exploded view of model MC-D18AI, MC-D21AI 86
No Description Part Code Note Qty Price Code MODEL: MC-D18AI, MC-D21AI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 Air outlet frame assy Cover of air outlet Water Tray Assy Evaporator Assy Top Cover Board Assy Left Side Plate Assy Sealplate sub-assy (evaporator) Seal of Letout Pipe Assy Front volute casing Rear volute casing Bottom Cover Plate Transformer Terminal Board Main Board Z6325L Capacitor CBB61 3uF 450V Electric Box Sub-Assy Electric Box As
Exploded view of model:MC-D24AI 88
No Description Part Code Note Qty Price Code MODEL: MC-D24AI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 Air outlet frame assy Cover Of Air-Out Water Tray Assy Evaporator Assy Top Cover Assy Left Side Plate Assy Sealplate sub-assy (evaporator) Seal of Letout Pipe Assy Front volute casing Rear volute casing Bottom Cover Transformer Terminal Board Main Board Z6325L Capacitor CBB61 Electric Box Sub-Assy Electric Box Assy Electric Box Cover Cover Of Fan
Exploded view of model: MC-C12AI, MC-C18AI Exploded view of panel for cassette MC-C12AI, MC-C18AI 90
No Description Part Code Note Qty Price Code 1 1 1 1 1 4 1 1 4 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 3 AQ AN AM BA AD AG BC AM AE AD AZ AT AD AC AC BB AE BH BH AE AW AX AH AC AK AD AE AY AZ AM AC AM AE AC AC AC AC 1 1 1 1 4 1 1 4 1 1 1 4 2 4 8 1 1 1 1 1 1 AE AE AE AB AD AB AC AH AZ AH AE AH AD AC AA AD AN AE AC AD AK MODEL: MC‐C12AI, MC‐C18AI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Seat Board Sub-Assy Front Side Plate Right baffle Assy Water Pump PSB-7 Pump Drainpipe Major Mount
Exploded view of model: MC-C24AI 92
No Description Qty Price Code 01382715 01432704 01332701 01302718 01302715 01222705 01302714 52012722 76712711 01702701 15704102 10312705 01074042 07210028 05232702 20182701 01412721 10372701 01399520 43110233 42011222 20102702 20122054 1 1 4 1 1 1 1 1 4 1 1 1 1 1 1 1 1 1 1 1 1 1 1 AD BA AC AN AM AX AM AU AC AH AZ AX AE AB AD BC AK AM AZ AH AD AD AE 390000453 1 AD 390001982G 20122055 20102703 30226340 33010027 01004641 01072703 49010104 43130324 01332752 01332702 45010201 05230026 01302716 3051004
Exploded view of model MC-F09AI 94
No Description Note Part Code MODEL: MC‐F09AI, MC‐F12AI 09 Fixed Mount 26909426R Louver Clamp 26112127 Guide Louver 10619403 Rotating Shaft 26909430 Front Connection Board 01349414P Base Frame 26909448 Induced air plate subassembly 02229418 Supporter 26909449 Mid‐clapboard sub‐assy 01249427 Front volute casing 26905205 Rear side plate assy 01319445 Centrifugal fan 10425200 Supporter 01809417 01319429 Right Side Plate Sub‐Assy Right Cover Plate 26909444 Left Pensile Bracket 01809401 Connection Board 01344
Exploded view of model: MC-F18AI 96
No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 Description Part Code MODEL: MC-F18AI Fixed Mount 26909426R Louver Clamp 26112127 Guide Louver 10619403 Rotating Shaft 26909430 Front Connection Board 01349414P Air Louver 10619404 Base Frame 26909448 Induced air plate subassembly 02229418 Supporter 26909449 Mid-clapboard sub-assy 01249416 Front volute casing 26905205 Rear side plate assy 01319430 Centrifug
Exploded view of model: MC-F24AI 98
No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 Description Part Code MODEL: MC-F24AI Cable-Cross Loop 76510021 Room Sensor 15KS-XH-2P 39000191 Louver Clamp 26112127 Guide Louver 10619403 Front Connection Board 01349414P Rotating Shaft 26909430 Air Louver 10619404 Base Frame 26909448 Induced air plate subassembly 02229418 Supporter 26909449 Mid-clapboard sub-assy 01249416 Front volute casing 26905205 Rear
Exploded view of model: MC-E36AI
No Description Part Code Note Qty MODEL: MC-E36AI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 Front Grill Cabinet Front Side Plate Sub-Assy Sensor Sub-assy Chassis Sub-assy Insulating Plate of Electric box Cover Pressure Protect Switch Compressor Mounting Plate Sub-Assy Compressor and fittings Connection Pipe Gas-liquid Separator Sub-Assy Bidirection Accumulator Connecting Pipe of Ushape Right Side Plate Sub-Assy Stra
No Description Part Code Note Qty MODEL: MC-E36AI 47 47 48 49 50 51 52 Motor Support Sub-Assy Motor Support Assy Left Side Plate Condenser support plate Clapboard Fan Motor Axial Flow Fan Jumper Connecting Cable Drainage Joint Electric Expand Valve Fitting Electric Expand Valve Fitting Electric Expand Valve Fitting Electric Expand Valve Fitting electrical heater Corrugated Pipe φ16 Left Handle Magnet Coil 01805402 01804240 01305064P 01895309 01244141 1570522801 10335010 4202300109 400205409 26113009
Exploded view of model: MC-E42AI
No Description Part Code Note Qty MODEL: MC-E42AI 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 Front Grill Cabinet Front Side Plate Sub-Assy Sensor sub-assy Chassis Sub-assy Insulating Plate of Electric box Cover Pressure Protect Switch Compressor Mounting Plate Sub-Assy Compressor and fittings Connection Pipe Gas-liquid Separator Sub-Assy Bidirection Accumulator Connecting Pipe of Ushape Right Side Plate Sub-Assy Stra
No Description Part Code Note Qty MODEL: MC-E42AI 47 48 49 50 Condenser support plate Clapboard Fan Motor Axial Flow Fan Electric Expand Valve Fitting Electric Expand Valve Fitting Electric Expand Valve Fitting Electric Expand Valve Fitting Left Handle Electric expand valve fitting Motor Support Assy Magnet Coil Magnetic Ring Terminal Board Drainage Plug Jumper Cap Magnetic Ring 01895309 01244141 1570522801 10335010 4300876710 4300876709 4300876708 4300876707 26235401 4300876705 01804240 4300040029 4