Backup section of this Guide for battery bank sizing when batteries power the essential loads sub-panel only.
Refer to the Discharge Example in Section 3 of this Guide for battery bank sizing when the batteries power both
the essential loads sub-panel and the main house breaker panel.)
Homeowners who do not have a net energy metering agreement use both Limited Power to Home and Time of
Use Selling modes to prioritize powering all loads (circuits both on the essential loads sub-panel and the main
house breaker panel) from the solar and/or batteries during programmed times. Refer to the Discharge Example
in Section 3 of this Guide for battery bank sizing when the batteries power both the essential loads sub-panel
and the main house breaker panel.
NOTE: Either the Grid Sell or the Limited Power to Home mode (check the appropriate box in the Grid Setup /
Grid Param menu) must be used in conjunction with Time of Use Selling.
During Time of Use Selling times, loads are powered from solar first (if available), batteries second, and the grid
third (if batteries have discharged to their programmed minimum SoC percentage level).
Make sure the GridCharge box is unchecked during peak pricing times so that the batteries do not charge when
energy from the utility company is most expensive (see Figure 7).