4.5.5 Limiter Sensor Wiring Connections
The Sol-Ark AccESS installation may include limiter sensors. Limiter sensors are required in the following
applications:
Limited to Home mode
Time of Use Selling mode
Systems that include both a generator and grid connection
Install limiter sensors on incoming electrical service wires L1 and L2, at the top of the main house breaker panel
(refer to Sol-Ark’s diagram within their manual).
Verify the limiter sensors’ proper sense and direction by adhering to the Sol-Ark manual’s “Testing and
Powering Up Sol-Ark” instructions in the Sol-Ark Manual. If applicable, perform the following checks after
completing Steps 1 and 2 outlined in the Basic Functional Test Section 4.5.6 below:
If MCU SW = 1654 or higher, an auto learn function avoids all this.
Using AC multi-meter, verify L1 voltage on AC in/out is 0Vac with main L1 connection in panel. Same
for L2.
To verify sensor connections to Sol-Ark, try removing one sensor from the main L1 connection. The
power should drop to 0W.
To verify proper sensor direction, with any loads in the home, the HM: +watts will be positive. If you
turn on solar panels and turn enable Grid Sell, you should see HM: -watts if you are producing more
power than the loads are consuming. And if you turn on limited power to Home mode, then HM: ~0
watts to zero the meter (system matches the loads to within 99%).