Installation Manual: 22.8kWh

SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 35 |
AccESS Sol-Ark System Solar PV Array Sizing
The Sol-Ark-12K’s built-in MPPT charge controller specifications are:
Quantity of built-in MPPT charge controllers per Sol-Ark-12K = 2
o Quantity of PV ports per MPPT charge controller = 2
o Total quantity of PV ports per Sol-Ark-12K = 4
MPPT charge controller starting voltage = 175V
DC
Maximum DC Voltage input per MPPT charge controller = 500V
DC
MPPT charge controller voltage range = 150-425V
DC
Maximum I
SC
current input per MPPT charge controller = 33A
Maximum operating current input per MPPT charge controller = 20A
Maximum battery charging current per Sol-Ark-12K = 185A
CAUTION: It is critical that the solar PV string’s voltage does not exceed 500V
OC
; voltage greater than
550V
DC
will damage the Sol-Ark equipment.
To properly configure solar PV modules to the Sol-Ark’s built-in charge controllers:
1. Due to the charge controller’s starting voltage of 175V
DC
, calculate the minimum number of solar
panel modules needed to meet this target voltage at the module’s maximum power voltage (V
MP
).
In this example, consider the Canadian Solar KuPower CS3K-300 solar PV module with a V
MP
of 32.5V
at Standard Test Conditions (STC).
Six modules in series are required to meet the charge controller’s minimum MPPT tracking
voltage requirement: 175V ÷ 32.5V = 5.4 (round up to the next whole number).
2. The charge controller’s maximum DC voltage input is 500V
DC
. Temperature affects the solar PV
module’s voltage output: voltage increases as temperature decreases. To calculate the maximum
number of solar panel modules in series per PV string, consider the module’s open circuit voltage (V
OC
)
rating, temperature coefficient and lowest expected temperature at the installation site.
In this example, the KuPower 300W module has a V
OC
of 39.3V at STC, a STC temperature of 25°C,
and a V
OC
temperature coefficient of -0.29%/°C.
To calculate the solar module’s V
OC
in an extreme low temperature condition of, say, -10°C:


󰇝
󰇟󰇛




󰇜
󰇛


󰇜󰇠󰇞



󰇝
󰇟󰇛

󰇜
󰇛

󰇜󰇠󰇞
Remember to convert the percentage value given as the V
OC
temperature coefficient to a decimal.


󰇝
󰇟󰇛

󰇜
󰇛

󰇜󰇠󰇞

 
󰇛

󰇜




󰇝
󰇟󰇛

󰇜󰇠󰇞

 


Eleven modules is the maximum allowable number of modules in series to prevent the solar
PV string from exceeding the charge controller’s maximum voltage input rating even in the
coldest weather conditions at the installation site: 500V ÷ 43.3V = 11.6 (round down to the
next whole number).
REV20210319