4.5.2 Making AC Connections
AC Landing Points Terminal Blocks
The AccESS is equipped with multiple knockouts on either side of the unit for accessibility to the Sol-Ark’s AC
connections. All AC connections are rated at 120/240 VAC. The bi-directional grid port can also support two
out of three phases of a 208 VAC grid connection (the two phases being L1 and L2, 120° out of phase).
The Sol-Ark equipment includes the following:
Bi-directional Grid Port (AC In/Out): 63A double-pole breaker
Bi-directional Generator Port: 63A double-pole breaker
Load Output (AC Out): 650A double-pole breaker
Figure 14.0 below shows the “Grid,” “Generator,” and “Load” connection locations. Also highlighted are the
neutral and ground AC terminal blocks.
Figure 14.0 - AC Power Input/Output Wiring Connection Points
Grid AC Wiring
1. Install a double pole 50A breaker in the main house breaker panel. Best practice dictates that this 50A
2P breaker be installed at the opposite end of the busbar from the main breaker (typically at the
bottom of the main house breaker panel).
2. Include an External AC Disconnect (with handle) between the 50A 2P breaker in the main house
breaker panel and the Sol-Ark’s “Grid” port.
The External AC Disconnect must be sized larger than 50A and include a knife blade switch.