Installation Manual: 22.8kWh
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 17 |
3.6 – Knock Out Locations
Three 1.375-inch OD knockouts and one 2-inch OD knockout are located on both sides of the AccESS cabinet.
They can be used for AC or DC inputs. Not all knockouts must be used.
Figure 5.0 – AccESS Cabinet Knockouts (sides)
3.7 – Pad Mounting
3.7.1 – Pad Requirements
The AccESS must be installed and secured on level concrete. For a pre-cast concrete pad, a 4” minimum
thickness is required. The pad should be 3” wider than the AccESS on all sides (34” x 22” x 4”).
The AccESS is not suited for wall mounting. Any attempt to wall mount the AccESS unit will Void the Warranty.
3.7.2 – Pad Mounting the SimpliPhi AccESS
Six 1-inch knockouts are located in the base of the AccESS for tool accessibility when mounting the AccESS to
the concrete pad. Cover knockout holes with sealing tape after pad mount installation, and prior to installing
the PHI 3.8 Batteries into the base of the cabinet. Not all knockouts have to be used, depending on the different
assets built into the AccESS system to meet the customer’s needs. Any attempt to wall mount the AccESS unit
will void the Warranty.
Secure the AccESS to the concrete with concrete anchors, such as threaded rods, masonry bolts, or carriage
bolts, minimum ½” diameter. Existing concrete floors in the garage or other areas are adequate “mounting pads”
if the thickness meets the 4” minimum thickness. See Figure 5.0 below for details.
REV20210319