Installation Manual: 22.8kWh
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 13 |
3.0 – Pre-Installation
The information within this section covers pre-installation procedures & considerations, namely, PHI 3.8
battery performance parameters to be aware of during the design process, guidance on system sizing, as well as
installation site requirements and pad mounting.
3.1 – PHI 3.8 Battery Performance Parameters and
Sizing Calculations
The PHI 3.8 batteries within the Sol-Ark AccESS are designed to operate at a continuous discharge rate of 11.4
kW
DC
across a large operating temperature range, as seen in Table 1.0 above. The SimpliPhi AccESS does not
require an increase in sizing nor any special compensations when determining the size of the energy storage
and management system under the circumstances and conditions seen in Table 1.0 above. Each AccESS unit
comes pre-programmed to maximize the performance of the PHI 3.8 battery bank. Settings are password
protected and require access to the lockout password by a qualified installer for modification.
PHI 3.8 batteries within the AccESS unit do not need to be de-rated unless running continuously at more than
90% capacity, at temperatures below 0° C, or above 45° C. To achieve higher, warrantied cycles of 10,000, the
PHI 3.8 batteries are operated at 80% maximum Depth of Discharge (DOD). The AccESS comes pre-
programmed for 80% DOD. Please contact SimpliPhi Power Technical Support if alternative settings are
desired. Please also refer to operating temperatures and inverter settings in this Manual’s Programming
section.
3.1.1 – Design Parameters: Maximum Sizing Guidelines
Below are the maximum sizing guidelines for installations of the AccESS:
• Maximum AC Grid input / output OCPD = 50 A double-pole
• Maximum DC coupled PV array = 13 kW
DC
(per Sol-Ark-12K)
• Maximum AC coupled PV array = 9.6 kW
AC
(per Sol-Ark-12K)
3.2 – System Sizing for Your Installation
The number of PHI 3.8 batteries within the AccESS unit(s) should be specified in terms of total rated storage
capacity and instantaneous power rating before the initial installation based on the goals and objectives of the
project. All PHI 3.8 batteries are balanced during final production and testing stages. Following proper wiring
guidelines ensures that a system will not require any manual balancing processes.
CAUTION: Do not combine PHI 3.8 batteries with other brands or chemistries.
CAUTION: Do not mix PHI 3.8 batteries from different installations, clients or job sites.
REV20210319