Installation
REV073019
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 34 |
5.3.4 – Auto Generator Start (AGS)
Table 6.0 – Programming Settings for SimpliPhi PHI 3.8 kWh 48V Battery
w/Schneider Auto Generator Start
AGS
10K Cycles
Warranty
5K Cycles
Warranty
3.5K Cycles
Warranty
Advanced
Settings > CFG
Trigger
80% DoD
90% DoD
100% DoD
Start DCV 30 sec
50.5V
49.8V
48V
Load
Enabled for the AccESS 1.0
Disabled (unnecessary) for 4 or more PHI 3.8’s
Strt Load
20A for the AccESS 1.0
Stop Load
18A for the AccESS 1.0
5.3.4 – PHI 3.8 Voltage Reference of Battery State of Charge
Figure 16.0 and Table 4.0 below depict the typical voltage levels (VDC) for the PHI 3.8 Battery at
various states of charge.
Figure 16.0 – PHI 3.8 C/2 Discharge Curve (typical)
Table 7.0
*Levels typical @ C/2
SOC
Voltage
100%
> 52.50 V
95%
51.70 V
90%
51.65 V
75%
51.40 V
50%
51.00 V
20%
50.20 V
10%
49.50 V
0%
48.00 V