and thus optimizing cycle-life. Updated firmware for an increased programmable LBCO range
may not be available in the Conext XW+.
Table 3.0 Programming Settings for SimpliPhi PHI 3.8 kWh 48V Battery
w/Schneider Electric Inverter XW Pro or XW+ 6848
INVERTER XW Pro or XW+
6848
10K Cycles
Warranty
5K Cycles
Warranty
3.5K Cycles
Warranty
Advanced Settings > Inverter
Settings
80% DoD
90% DoD
100% DoD
Low Battery Cut-Out Voltage
1
48V
(50.5V Recommended)
48V
(49.8V Recommended)
48V
LBCO Hysteresis
2.0V
LBCO Delay
10 Sec
High Batt Cut Out
60V
Search Watts
Default
Search Delay
Default
Charger Settings > Custom
Settings
Batt Type
Lithium Ion
Lithium Ion
Control
2StgNoFloat
Bulk Voltage
54.4V
54.4V
56V
MaxBulkCurrent (C/2)
2
37.5A per PHI3.8; (112.5A for 3, 150A for 4)
DisChgImax
2
60A per PHI3.8; (180A for 3, 240A for 4)
To calculate as a percentage, divide the relevant Amp value by
140A (128% for 3, 171% for 4)
DisChgImax Timer
s
Batt Capacity
2
75Ah per PHI3.8; (225Ah for 3, 300Ah for 4)
Max Charge Rate (C/2)
2
37.5A per PHI3.8; (112.5A for 3, 150A for 4)
To calculate as a percentage, divide the relevant Amp value by
140A (80% for 3, 100% for 4 or more)
Default Batt Temp
Warm
Recharge Volts
50.6V
Absorb Time
60 Minutes
Notes:
1. Maximum setting of 48V limited by some inverter firmware is below the recommended setting.
2. Per PHI 3.8 Battery These setting are calculated by multiplying the nominal per battery value times the # of batteries.
3. Levels are typical @ 25C and may need adjusting at temperature extremes.
4. When performing rapid deep charge/discharge cycles the battery should be allowed to "rest" 15 minutes in between.