Installation

REV073019
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 28 |
5.0 Programming
5.1 Depth of Discharge
The AccESS comes pre-programmed for 80% depth of discharge (DoD), assuming the AccESS is
connected to an AC power source such as the grid or a generator. This qualifies for the 10-year / 10,000
cycle Warranty on the PHI 3.8 Batteries.
To change the DoD to the 5,000 cycle Warranty or 3,500 cycle Warranty, modify the voltages in the Basic
Settings and Advanced Settings per the Programming section. Refer to the PHI 3.8 Battery Warranty.
If a firmware update is executed on the AccESS, please verify all PHI custom settings are still in place.
These settings can be found at the end of this manual in Section 7.0: Operating Parameters.
5.2 Configuring the Schneider Electric Conext XW+
The Schneider Electric Conext XW Pro or XW+ is capable of many different modes of operation via
configurable settings. This includes:
AC Input Settings
Grid Support Settings
Prioritizing and Managing Energy Sources
Generator Support Settings
Auxiliary Output Settings
These settings can be modified to support the function the owner would like to achieve with the AccESS
unit. To configure the AccESS, please refer to Schneider Electric’s Conext XW Pro or XW+
Inverter/Charger Owner’s Guide.
The Schneider Electric Owner’s Guide contains information and procedures necessary for configuring,
operating, maintaining, and troubleshooting the Schneider Electric Conext XW Pro or XW+
Inverter/Charger. The guide is intended for anyone who needs to operate, configure, and troubleshoot the
inverter. Certain configuration tasks should only be performed by qualified personnel.
5.3 Operating Parameters Per Warranty
Although the PHI 3.8 Batteries within the AccESS unit are capable of performing at very high rates and
depths of discharge within a very wide temperature range, in order to achieve extended life cycles and to
comply with the Warranty, the operating parameters, indicated in Tables 3.0 and 4.0 below, must be
adhered to. The parameters shown in Table 3.0 below must be applied based on desired Warranty/cycle
life. The AccESS comes pre-programmed for 80% depth of discharge.
5.3.1 Inverter Programming Settings
Schneider Electric Conext XW Pro or XW+ Inverter/Charger
The Schneider Electric Conext XW Pro or XW+ Inverter/Charger has a firmware limitation that
creates a potential issue with Lithium-Ion batteries: the Low Battery Cut-Out Voltage (LBCO)
setting is limited to 48V maximum. This value is below the recommended LBCO settings to
maximize cycle-life of most Lithium-Ion batteries including PHI 3.8 Batteries. Per the Warranty, a
48V LBCO corresponds to 100% DoD and maintains a much more limited cycle life.
Until Schneider releases updated firmware to adjust this setting above 48V in the Conext XW Pro,
this issue can be largely mitigated by setting the “Recharge Volts” above the desired LBCO
thresholds as outlined Table 1.0 above. Therefore, systems that do not rely solely on renewable
energy (i.e. grid tied systems, AGS systems) will typically start charging the PHI 3.8 Batteries
once the recharge voltage level is reached, preventing further discharge of the PHI 3.8 Batteries