Figure 8.0 – Optional Generator Installation/Connection Diagram 
Inverter Charger Grounding 
The Conext XW Pro or XW+ is provided with ground terminals that must be reliably connected to 
ground (protective earth) by appropriately sized equipment grounding conductors. System 
grounding for the AC and DC systems must be done according to all applicable NEC and local 
installation codes. 
Feed-in Protection Requirements 
The amount of power that can be fed into a distribution panel and the means and location for 
feed-in, must be in accordance with NEC 2017 article 690.64 or the current requirements of the 
local electrical code. 
Failure to follow these instructions can result in damage to equipment and void the Warranty.  