Integration Guide
REV0226
18
SimpliPhi Power, Inc. | 420 Bryant Circle | Ojai, CA 93023, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 7 |
4.4 – FLEXnet DC Settings
Table 3.0 - Settings for SimpliPhi PHI 3.5 kWh 48V Battery w/Outback FLEXnet DC
FLEXnet DC Settings
10k Cycles
(80% DoD)
5k Cycles
(90% DoD)
3.5k Cycles
(100% DoD)
FNDC Battery Ah
1
138Ah / 69Ah
FNDC Charge Voltage (V)
27.6 / 55.2
28.2 / 57
28.2 / 57
FNDC Charged Return Amps
8A / 4A
FNDC Battery Charge Factor
98%
FNDC Relay Invert Logic No
FNDC Relay Voltage High/Low
High = 26.5/53, Low = 28.8/49.6
FNDC Relay SOC High/Low
SOC High = 0%, SOC Low = 0%
FNDC Relay Delay
High = 1, Low = 0
Notes:
• 1. Per PHI 3.5 kWh battery – These settings are calculated by multiplying the nominal per battery value
times the # of batteries. Refer to Charge Controller Bank Sizing under the “Battery Bank Sizing” section.
•
Levels are typical @ 25C and may need adjusting at temperature extremes.
• When performing rapid deep charge/discharge cycles the battery should be allowed to "rest" 15 minutes in
between.
CAUTION: When PHI battery quantities change, the capacity & charge/discharge current settings
must be reassessed. Failure to do so will void the Warranty.
4.5 – MATE3/MATE3s Settings
Table 4.0 - Program Settings for SimpliPhi PHI 3.5 kWh 48V Battery w/Outback MATE3/MATE3s
MATE3 / MATE3s Settings
10k Cycles
(80% DoD)
5k Cycles
(90% DoD)
3.5k Cycles
(100% DoD)
FLEXnet DC Advanced Control Low SOC Warning = 20%
FLEXnet DC Advanced Control Critical SOC Warning = 10%
Notes:
• Levels are typical @ 25C and may need adjusting at temperature extremes.
• When performing rapid deep charge/discharge cycles the battery should be allowed to "rest" 15 minutes in
between.
CAUTION: When PHI battery quantities change, the capacity & charge/discharge current settings
must be reassessed. Failure to do so will void the Warranty.