A-4PHI-OB Installation
REV0720
18
SimpliPhi Power, Inc. | 420 Bryant Circle | Ojai, CA 93023, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 5 |
1.2 – Safety & Protective Features
1.2.1 – 80A Breaker
All PHI 3.5 Batteries within the AccESS unit are outfitted with an 80A hydraulic/magnetic circuit
breaker. This breaker increases safety during shipping and installations and allows the PHI 3.5
Battery to effectively be turned “OFF” or “ON.” The breaker works in conjunction with the built-in
battery management system (BMS) and creates additional safety, efficiency and functionality to
the overall power storage system.
Figure 1.0 - PHI 3.5 kWh 48V Circuit Breaker
CAUTION:
Circuit Breakers, Disconnects and Fuses should be employed throughout several points of a
power storage and generation installation to effectively isolate and protect all components of the system
to safeguard against faults, short circuits, polarity reversals or a failure of any component in the overall
system. Fuses, breakers, wiring ratings and values should be determined by established standards and
evaluated by certified electricians, licensed installers, and regional code authorities. Although each PHI
3.5 Battery contains both a circuit breaker and an internal BMS with circuitry that protects the Lithium
Ferrous Phosphate cells from overcharge, over-discharge and extreme load amperage, the PHI 3.5
Batteries must always be installed with a charge controller and the appropriate settings to protect the PHI
3.5 Battery from open PV voltage and other high voltage charging sources. The PHI 3.5 Battery
Management System (BMS) and internal circuit breaker alone will not protect the PHI 3.5 Batteries from
these extreme electrical phenomena. Failure to adhere to installation protocol will void the Warranty.
CAUTION:
Verify polarity at all connections with a standard volt meter before 1) energizing the system
and 2) turning the PHI 3.5 circuit breaker “ON/OFF” switch to the “ON” position.
Reverse polarity
at the
battery terminals will void the Warranty and destroy the PHI 3.5 Batteries.
PHI 3.5 Batteries pose some risk of shock or sparking during the installation and initial wiring and
connection process. This is consistent with all other battery-based storage formats. Be sure to turn the
built-in breaker to the “OFF” position to minimalize the risk of shock or sparks during the installation and
commissioning of the system. Use of insulated gloves, clothing and footwear is always recommended
when working in close proximity to electrical devices. Cover, restrain or remove jewelry or conductive
objects (metal bracelets, rings, belt buckles, metal snaps, zippers, etc.) when working with any electrical
or mechanical device. Cover or restrain long hair and loose clothing when working with any electrical or
mechanical device.