A-4PHI-OB Installation

REV0720
18
SimpliPhi Power, Inc. | 420 Bryant Circle | Ojai, CA 93023, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 18 |
5.3.5 – PHI 3.5 Voltage Reference of Battery State of Charge
Figure 6.0 and Table 5.0 below depict the typical voltage levels (VDC) for the PHI 3.5 Battery at
various states of charge.
Figure 6.0PHI 3.5 C/2 Discharge Curve (typical)
Table 5.0
SOC
Voltage*
100%
> 52.50 V
95%
51.70 V
90%
51.65 V
75%
51.40 V
50%
51.00 V
20%
50.20 V
10%
49.50 V
0%
46.00-48.00 V
*Levels typical @ C/2