A-4PHI-OB Installation
REV0720
18
SimpliPhi Power, Inc. | 420 Bryant Circle | Ojai, CA 93023, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 17 |
CAUTION: When PHI battery quantities change, the capacity & charge/discharge current settings
must be reassessed. Failure to do so will void the Warranty.
5.3.3 – Battery Monitor
Table 4.0
FLEXnet DC Settings
10k Cycles
(80% DoD)
5k Cycles
(90% DoD)
3.5k Cycles
(100% DoD)
FNDC Battery Ah
1
138Ah / 69Ah
FNDC Charge Voltage (V)
27.6 / 55.2
28.2 / 57
28.2 / 57
FNDC Charged Return Amps
8A / 4A
FNDC Battery Charge Factor
98%
FNDC Relay Invert Logic
No
FNDC Relay Voltage High/Low
High = 26.5/53, Low = 28.8/49.6
FNDC Relay SOC High/Low
SOC High = 0%, SOC Low = 0%
FNDC Relay Delay
High = 1, Low = 0
Notes:
• 1. Per PHI 3.5 kWh battery – These settings are calculated by multiplying the nominal per battery value
times the # of batteries. Refer to Charge Controller Bank Sizing under the “Battery Bank Sizing” section.
• Levels are typical @ 25C and may need adjusting at temperature extremes.
• When performing rapid deep charge/discharge cycles the battery should be allowed to "rest" 15 minutes in
between.
CAUTION: When PHI battery quantities change, the capacity & charge/discharge current settings
must be reassessed. Failure to do so will void the Warranty.
5.3.4 – MATE3/MATE3S Settings
Table 5.0
MATE3 / MATE3s Settings
10k Cycles
(80% DoD)
5k Cycles
(90% DoD)
3.5k Cycles
(100% DoD)
FLEXnet DC Advanced Control
Low SOC Warning = 20%
FLEXnet DC Advanced Control
Critical SOC Warning = 10%
Notes:
• Levels are typical @ 25C and may need adjusting at temperature extremes.
• When performing rapid deep charge/discharge cycles the battery should be allowed to "rest" 15 minutes in
between.
CAUTION: When PHI battery quantities change, the capacity & charge/discharge current settings
must be reassessed. Failure to do so will void the Warranty.