A-4PHI-OB Installation
REV0720
18
SimpliPhi Power, Inc. | 420 Bryant Circle | Ojai, CA 93023, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 12 |
Figure 4.0 – AccESS Unit Clearances
3.6 – Knock Out Locations
Three 1-inch OD knockouts and one 1.5-inch OD knockout are located on both sides of the AccESS
cabinet. They can be used for AC or DC inputs. Not all knockouts may be used.
3.7 – Pad Mounting
3.7.1 – Pad Requirements
The AccESS must be installed and secured on level concrete. For a pre-cast concrete pad, a 4”
minimum thickness is required. The pad should be 3” wider than the AccESS on all sides (34” x
22” x 4”).
The AccESS is not suited for wall mounting. Any attempt to wall mount the AccESS unit will void
the Warranty.
3.7.2 – Pad Mounting the SimpliPhi AccESS
Six 1-inch knockouts are located in the base of the AccESS for tool accessibility when mounting
the AccESS to the concrete pad. Cover knockout holes with sealing tape after pad mount