Installation
REV073019
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 30 |
Note: Instead of the Lithium Ion sub-menu, the Custom battery menu may be used instead.
In this case, use the following settings:
Table 4.0 – Programming Settings for SimpliPhi PHI 3.8 kWh 48V Battery
w/Schneider Electric Inverter XW Pro or XW+ 6848
INVERTER – XW Pro or XW+
6848
10K Cycles
Warranty
5K Cycles
Warranty
3.5K Cycles
Warranty
Advanced Settings > Inverter
Settings
80% DoD
90% DoD
100% DoD
Low Battery Cut-Out Voltage
1
48V
(50.5V Recommended)
48V
(49.8V Recommended)
48V
LBCO Hysteresis
2.0V
LBCO Delay
10 Sec
High Batt Cut Out
60V
Charger Settings > Custom Settings
Batt Type
Custom
Custom
Eqlz Support
Disabled
Bulk Voltage
54.4V
54.4V
56V
Absorb Voltage
54.4V
54.4V
56V
Float Voltage
N/A (disabled); 54V may be used as a placeholder value
Batt Temp Comp
0 mv/C
Batt Capacity
2
75Ah per PHI3.8; (225Ah for 3, 300Ah for 4)
Max Charge Rate (C/2)
2
37.5A per PHI3.8; (112.5A for 3, 150A for 4)
To calculate as a percentage, divide the relevant Amp value by 140A
(80% for 3, 100% for 4 or more)
Charge Cycle
2-Stage
Default Batt Temp
Warm
Recharge Volts
50.6V
Absorb Time
60 Minutes
Note: Consider Charge Block Start and Charge Block Start in the inverter’s Advanced Settings >
Charger Settings menu. If this system includes a grid connection to a utility with higher electricity rates
during certain peak times, it is recommended to set the Charge Block window during peak utility rate
hours. If the batteries reach their ReCharge Volts setting during the Charge Block window, the batteries
will not recharge from the grid until the end of the Charge Block time period; the batteries are still able to
charge from a connected charge controller or generator during this window.