Installation

REV073019
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 22 |
4.5.3 AC System Bonding
Multiple AC Neutral-to-Ground Bonds
Verify that only one neutral-to-ground bond exists in the system. Having more than one neutral-
to-ground bond in a system violates local electrical codes, may create a shock or fire hazard, and
may cause some sensitive equipment to malfunction.
Failure to follow these instructions can result in death or serious injury and will void the
Warranty.
System bonding refers to connection (bonding) of one of the current-carrying conductors of an
electrical system to ground. This creates a "grounded conductor" or "neutral" that is at ground
potential, but is separate from the equipment ground conductor. System bonding must be done at
only one location. Procedures for system bonding vary between on-grid and off-grid systems.
System bonding for on-grid systems
The Conext XW Pro or XW+ does not connect the neutral to ground. The AC input neutral is
already bonded to ground by the incoming utility grid system. Do not connect the neutral to
ground in any additional location.
The Conext XW Pro or XW+ does not switch or disconnect the AC neutral in any mode of
operation, so even in invert (back-up) mode, the inverter load sub-panel neutral is bonded to
ground by the utility grid system. It must not be grounded again in the inverter load sub-panel.
System bonding for off-grid systems
In a system without a generator, or with a generator that does not provide a grounded neutral,
you must make the connection from neutral to ground in the inverter load sub-panel or main
distribution panel, as applicable.
In a system with a generator that provides a grounded neutral, no additional connection from
neutral to ground is needed. Do not connect neutral to ground in the inverter load sub-panel or
main distribution panel, as applicable.
For more information regarding installations with a generator, please refer to Schneider Electric’s
manual for the AGS.
4.5.4 Making DC Connections
This section only applies to AccESS systems equipped with the optional Conext MPPT 80 600
Solar Charge Controller. Refer to the Conext MPPT 80 600 Owner’s Guide for further information
regarding functionality programming of the charge controller.
Note: Before connecting PV, verify the cable polarity and mark the cable accordingly as Positive
or Negative.
The SimpliPhi AccESS is equipped with multiple knock outs.
Bring the PV wiring from the PV disconnect into the AccESS enclosure through the
appropriate knock out for PV IN.
Strip 0.5” of insulation from the Positive PV Conductor(s). (1.27 cm).
Insert the stripped conductor end into the terminal of the MPPT.
Repeat for the Negative PV Conductor(s)