Installation

REV073019
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 21 |
Figure 8.0 Optional Generator Installation/Connection Diagram
Inverter Charger Grounding
The Conext XW Pro or XW+ is provided with ground terminals that must be reliably connected to
ground (protective earth) by appropriately sized equipment grounding conductors. System
grounding for the AC and DC systems must be done according to all applicable NEC and local
installation codes.
Feed-in Protection Requirements
The amount of power that can be fed into a distribution panel and the means and location for
feed-in, must be in accordance with NEC 2017 article 690.64 or the current requirements of the
local electrical code.
Failure to follow these instructions can result in damage to equipment and void the Warranty.