PHI 3.8 24V & 48V Battery Manual

REV073019
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 17 |
Although the PHI battery charges to the voltages outlined above, the battery “rests” at
approximately 13.3V / 26.7V / 53.3V. Refer to Table 6.0 below for a complete Battery Voltage
versus State of Charge (SOC) gauge.
Table 6.0 Battery Voltage VS. State of Charge (SOC)
SOC
12V
24V
48V
100%
> 13.13 VDC
> 26.25 VDC
> 52.5 VDC
95%
12.93
25.9 VDC
51.7 VDC
90%
12.91
25.8 VDC
51.65 VDC
75%
12.85
25.7 VDC
51.4 VDC
50%
12.75
25.5 VDC
51.0 VDC
20%
12.55
25.1 VDC
50.2 VDC
10%
12.38
24.8 VDC
49.5 VDC
0%
12.0
24.0 VDC
48.0 VDC
CAUTION: Verify polarity at all connections before energizing system. Reverse polarity at the PHI Battery
terminals will void the Warranty and destroy the PHI Batteries.
CAUTION:
Before commissioning the system the appropriate controller and inverter settings must be
programmed per the manufacturer’s recommendations. Consult the manufacturer’s manuals and/or the
Integration Guides listed on SimpliPhi’s Product Documentation web page (Schneider, Magnum,
Outback, etc.). The following Charge Controller Integration tables are for general reference only.
CAUTION:
All SimpliPhi Power Core Power and Peak Power products are designed to work exclusively in
parallel. Never connect in series to achieve higher voltages
.
6.0 SimpliPhi Technical Support
For technical support related to your PHI Battery, please contact us as follows:
805.640.6700
techsupport@simpliphipower.com