5.0 Programming
5.1 Operating Parameters Related to Cycle Life
To maintain optimal PHI Battery health and longevity, adhere to the operating parameters outlined in Tables 5.0 and 6.0 below.
Refer to the manufacturer-specific Integration Guide from SimpliPhi’s Product Documentation web page for a complete list of
settings: https://simpliphipower.com/product-documentation/.
Table 5.0Optimal Operation Parameters
Recommended Operating Conditions for 10 Year Warranty
Equivalent to 80% Retained Capacity 10,000 cycles 5,000 cycles 3,500 cycles
Depth of Discharge (DoD) 80% 90% 100%
Operating Temperature °F (°C) 32 to 120 (0 to 49)
Programming Settings for Ancillary
Equipment
24V 48V 24V 48V 24V 48V
Low Battery Cut-Off Voltage (V) 25.1 50.2 24.8 49.6 24 48
Absorb / Charging Voltage
24V 48V
28V 56V
Absorb Time 6 minutes (0.1 Hours)
Absorb End Amps (if applicable) 2% of the PHI Battery bank’s total Ah capacity
Table 6.0Operating Limitations
Notes / Operating Limitations for PHI Batteries
PHI 3.8-M
Limitations by Model 48V 24V
Continuous Discharge Rate (ADC) 37.5 75
Surge Discharge Rate (ADC)
10 minutes maximum
80
Continuous Charge Rate (ADC) 37.5 75
Levels are typically @ 25°C and may need adjusting at temperature extremes.
When performing rapid deep charge/discharge cycles, the PHI Battery should be allowed to “rest” 15 mins in between.
Although the PHI battery charges to the voltages outlined above, the battery “rests” at approximately 26.7V / 53.3V. Refer to
Table 6.0 below for a complete Battery Voltage versus State of Charge (SOC) gauge.