Bat QTY PHI 3.8 / 48V (37.5ADC) 1 x XW+ 5548 (110ADC charger) 1 x XW+6848 (140ADC charger)
2 75A 68% 53%
3 112.5A 100% 80%
4
150A
100%
100%
• Levels are typical @ 25⁰C and may need adjusting at temperature extremes.
• When performing rapid deep charge/discharge cycles the battery should be allowed to "rest" 15 minutes in between.
• Always refer to the SimpliPhi Power Manual and Warranty for the specific PHI battery model.
CAUTION: When PHI battery quantities change, the capacity & charge/discharge current
settings must to be reassessed. Failure to do so will void the Warranty.
4.3 – MPPT Charge Controller Settings
Solar charge controllers must be used in DC coupled systems to regulate the power produced by the PV array
that is delivered to the batteries. Schneider Electric offers two different MPPT charge controllers, both of
which are compatible with PHI batteries:
1. Conext MPPT 80 600
2. Conext MPPT 60 150
The 80 600 model is somewhat unique in that allows for larger strings of PV modules to be easily installed and
connected to the PHI battery bank. Charge controller selection depends on the system size and personal
preference; The recommended setpoints for either Schneider Electric charge controller are the same.
SimpliPhi Power recommends the 80% DoD settings in Table 2.0 below in order to maximize the Warranty.
Additional settings are outlined based on Warranty and desired cycle life.
Table 2.0 - Settings for SimpliPhi PHI 3.8 kWh 24V & 48V Battery w/Schneider XW MPPT60/80
Conext MPPT60 / 80 Settings
Advanced Settings > Charger Settings
Batt Type
Custom
Custom Settings
Eqlz Supt Disabled
Bulk Voltage
28V / 56V
Absorb Voltage 28V / 56V
Float Voltage
27V / 54V
Batt Temp Comp 0mV/C
Batt Capacity
2
151Ah (per PHI 3.8 24V) / 75Ah (per PHI 3.8 48V)
Max Charge Rate (C/2)
2,3
75A (per PHI 3.8 24V) / 37.5A (per PHI 3.8 48V)
Charge Cycle
3 Stage
ReCharge Volts 25.6V / 51.2V
Absorb Time
.1 Hours (6 minutes)
Default Batt Temp Warm
Batt Voltage (Auto-detected)
24V / 48V
Aux Settings
Not Used
…
Default
Notes:
•
1.
Maximum setting of 48V limited by some inverter firmware is below the recommended setting.