6. Wire the pre-scaler board to the battery monitor using the provided orange networking cable.
7. Include the battery monitor in the remainder of the Schneider system’s network via the Xanbus
networking cable.
Table 3.0 - Settings for SimpliPhi PHI 3.8 kWh 48V Battery w/Schneider Conext Battery Monitor
Conext Battery Monitor Settings
Setting
Value
Capacity
2
75Ah (per PHI 3.8)
Discharge Rate
20 Hrs
Nominal Temp 67F
Shunt Amps
500
Shunt mV
50
Self Disch
<1%/Month
Discharge Floor 20%
Float Voltage
53.32
Float Amps 2%
Auto Sync Time
240 Sec
Temp Unit
Celsius
Back Light Timer
30 Sec
Peukert Expo 1.05
Charge Eff Mode
Automatic
Temp Coeff 0.5Ah/degC
Default Temp
76 Deg F
Sync Sensitivity
5
Time Rem Filter
Faster
CAUTION: When PHI battery quantities change, the capacity & charge/discharge current
settings must be reassessed. Failure to do so will void the Warranty.