Magnum Energy Integration Guide
Table Of Contents
REV
20201125
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93030, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 9 |
General
80% DOD
90% DOD
100% DOD
Connect Volts 25.1V / 50.2V for 80% DOD 24.8V / 49.5V for 90% DOD
Disconnect Volts
4
27.2V / 54.4V
02E AC In – SOC
ME-BMK is required for this setting
The
02D AC In – VDC
setting is preferred over
02E AC In - SOC
Connect SOC 20%
Disconnect SOC 100%
02F Power Up Always OFF
03 Charger Setup
03C Battery Type CC/CV
Max Charge Amps
1
(ADC)
75A
per PHI3.8 24V
37.5A
per PHI3.8 48V
CV Charge Volts (VDC) 28V / 56V
CV Chg Done Time
.1 Hr. (6 Minutes)
(set to “Hold CV Chg VDC” when generator charging)
CV Chg Done Amps (ADC)
2% of the PHI Battery bank’s capacity
Max CC/CV Time (Hrs.) 12 Hrs.
Recharge Volts (VDC) 25.3V / 50.6V
03D Absorb Done Time CC/CV Controlled
03E Max Charge Rate
3
(%)
75A
per PHI3.8 24V (see footnote 3 for % calculation)
37.5A
per PHI3.8 48V (see footnote 3 for % calculation)
03F Max Charge Time CC/CV Controlled
03G Final Charge Stage CC/CV Controlled
Rebulk Volts (VDC) 25.3V / 50.6V
03H EQ Reminder Days OFF
Notes:
1.
Per PHI 3.8 kWh battery – These settings are calculated by multiplying the nominal per-battery value times
the number of batteries.
2.
The maximum programmable setting of 48.8V is below the recommended LBCO setting. To maintain the
batteries at a maximum 80% or 90% DOD, utilize the
02D AC In – VDC
setting for grid backup.
3.
Per PHI 3.8 kWh battery and as a percentage of the inverter’s or charge controller’s maximum charge
rating – These settings are calculated by multiplying the nominal per-battery value times the number of
batteries, then divide by the equipment’s maximum charging current.
Battery
Quantity
PHI 3.8 / 24V
(45ADC)
1 x MS4024PAE
charge rate
(105ADC charger)
1 x PT-100
charge rate
(100ADC)
PHI 3.8 / 48V
(37.5ADC)
1 x MS4448PAE
charge rate (60ADC
charger)
1 x PT-100
charge rate
(100ADC)
2
150A
85%
100%
75A
100%
75%
3
225A
100%
100%
112.5A
100%
100%
4
300A
100%
100%
150A
100%
100%
•
Levels are typical @ 25C and may need adjusting at temperature extremes.
• When performing rapid deep charge/discharge cycles, the battery should be allowed to "rest" 15 minutes in between
CAUTION:
When PHI battery quantities change, the capacity and charge/discharge current
settings must be reassessed. Failure to do so will void the Warranty.