Victron Energy Integration Guide

REV070219
SimpliPhi Power, Inc. | 3100 Camino Del Sol | Oxnard, CA 93023, USA | (805) 640-6700 | info@simpliphipower.com | SimpliPhiPower.com
| 9 |
4.2 PHI 3.8 General Settings with Victron
The general program settings for the PHI 3.8 Batteries with Victron products are outlined below.
Table 1.0 - Settings for SimpliPhi PHI 3.8 kWh 24V / 48V Battery w/Victron
General
10k Cycles
(80% DoD)
5k Cycles
(90% DoD)
3.5k Cycles
(100% DoD)
Battery Curve
Fixed
Capacity
1
(Ah)
151Ah per PHI3.8 24V; (302Ah for 2, 453Ah for 3)
75Ah per PHI3.8 48V; (150Ah for 2, 225Ah for 3)
Absorb Voltage (V)
27.2 / 54.4
27.2 / 54.4
28 / 56
Absorb Time
1 Hour
Float Voltage (V)
27 / 54 (typically Disable)
Discharge Voltage "LBCO" (V)
25.1 / 50.2
24.8 / 49.6
24 / 48
Re-Charge (V)
25.3 / 50.6
Max Discharge/Charge Current (C/2)
1
45A per PHI3.8 24V; (90A for 2, 135A for 3)
37.5A per PHI3.8 48V; (75A for 2, 112.5A for 3)
Peukert Expo
1.05
Charge Efficiency
95%
SoC when Bulk Finished
95%
Notes:
1. Per PHI 3.8 Battery These settings are calculated by multiplying the nominal per battery value times the #
of batteries.
Levels are typical @ 25°C and may need adjusting at temperature extremes.
When performing rapid deep charge/discharge cycles, the PHI Battery should be allowed to "rest" 15 minutes
in between.
Always refer to the SimpliPhi Power Manual and Warranty for the specific PHI Battery model.
4.3 Victron BMV-700 Programming Settings
Table 2.0 - Settings for SimpliPhi PHI 3.8 kWh 48V Battery w/Victron BMV-700 Battery Monitor
Victron BMV-700 Settings
PHI 3.8 kWh 24V / 48V
Quick Start
Battery Capacity
1
(Ah)
151Ah per PHI3.8 24V; (302Ah for 2, 453Ah for 3)
75Ah per PHI3.8 48V; (150Ah for 2, 225Ah for 3)
Charged Voltage (V)
26.5 / 53.2
Tail Current (%)
4
Charge Detection Time (minutes)
1
Peukert Exponent
1.05
Charge Efficiency Factor (%)
98
Current Threshold (A)
0.1
Time to go Averaging Period (minutes)
3
Notes:
1. Per PHI 3.8 Battery These settings are calculated by multiplying the nominal per battery value times the #
of PHI Batteries.
Levels are typical @ 25°C and may need adjusting at temperature extremes.
When performing rapid deep charge/discharge cycles, the PHI Battery should be allowed to "rest" 15 minutes
in between.
Always refer to the SimpliPhi Power Manual and Warranty for the specific PHI battery model.
CAUTION: When battery quantities change, the capacity current settings must to be reassessed.